Examples under OATH infraction code 102
535 distinct enforcement-description examples carrying this infraction code. Check the actual summons before interpreting the code.
- Means of egress and exit protection · 39163949XSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION - GROUND FLOOR/BSMT APT OBSERVED WITH OBSTRUCT
- Masonry or façade deterioration · 39202525LSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION, INSPECTOR ON DUTY NOTICED SEVERAL VERTICAL AND HORIZONTAL CRACKS AND LOOSE BRICK AT EXP 1, REPAIR AND/REPLA
- Masonry or façade deterioration · 39202637XSection 28-301.1 / OATH code 102 · ATOI OBSERVED MULTIPLE STEP CRACKS, DETERIORATED MORTOR JOINT, SPALLING BRICKS AT EXPOSURE#1(EAST 6 STREET), REPAIR AND/REPLACE
- Plumbing fixture and drainage configuration · 39202473ZSection 28-301.1 / OATH code 102 · ATOI OBSERVED HOT WATER HEATER ON THE ROOF INSTALLED WITH NO DISCHARGER PIPING INSTALLED COMING OUT OF THE PRV CONTRARY TO PC 504.
- Safe building maintenance · 39202466KSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED HOLE PENETRATIONS, (PLASTIC ACCESS PANELS) .LOCATED THROUGHOUT THE
- Street / sidewalk occupancy and dot authorization · 35733231NSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. SUBJECT IS A 2-STORY ON A CORNER LOT WITH COMMERCIAL USE OCCUPANCY. EXP.
- Street / sidewalk occupancy and dot authorization · 35733230LSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. SUBJECT IS A 3-STORY ON A CORNER LOT WITH STORE BUILDING USE. EXP 1 IS AL
- Windows, doors and openings · 35718726JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. I OBSERVED HAZARDOUS CONDITION WITH THE EXTERIOR WALL OF THE BUILDING. AT V
- Means of egress and exit protection · 39202745NSection 28-301.1 / OATH code 102 · ATOI OBSERVED AIR-CONDITIONED S IN BASKETS OF FIRE ESCAPE ANOTHER WITHOUT SUPPORT BRACKETS AT EXPOSURE #1 OF ABOVE PREMISES; IMPEE
- Authorized use versus observed occupancy · 39202904LSection 28-301.1 / OATH code 102 · FTM BLDG WALL(S) OR APPURTENANCES. OBSVED AT EXPO 2 AT ALLEYWAY FIRE RATED WALL AT EXISTING DWELLING UNIT HAS AN OPENING APPROX 4F
- Masonry or façade deterioration · 39202810KSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. FACADE EXP 1,2,3 HAS STEP/VERTICAL CRACKS, MISSING BRICK/MORTAR. SHARED DRI
- Fire prevention or detection system · 39202967ZSection 28-301.1 / OATH code 102 · ATOI OBSERVED IN THE BASEMENT LACK OF SPRINKLER COVERAGE IN A OPEN AREA ROOM CONTAINING GARBAGE BINSBC 903.3.3 OBSTRUCTED LOCATION
- Authorized use versus observed occupancy · 39202969MSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED HOLE PENETRATIONS AND PLASTIC ACCESS PANELS, WHICH ARE NOT RATED.
- Windows, doors and openings · 39202988HSection 28-301.1 / OATH code 102 · FTM: AT THE TIME OF INSPECTION, OBSERVED ENTIRE STRUCTURE IN SEVERE DETERIORATED AND UNSAFE CONDITION. ROOF WITH LARGE SECTIONS OP
- Masonry or façade deterioration · 39202851RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN INTERIOR WALLS, CEILINGS AND EXTERIOR FACADE. AT TIME OF INSPECTION, OBSERVED CRACKED CEILINGS WITH EVIDENCE O
- Masonry or façade deterioration · 39202927YSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED AT EXP#2 MISSING MORTAR JOINTS AT MULTIPLE LOCATIONS, CRACKS ON FACADE AT EXP#1 AND 2, AT EXP# 4 PA
- Masonry or façade deterioration · 35718653HSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. PROPERTY IS AN ATTACHED 1 STORY HEALTH CENTER LOCATED ON AN INTERIOR LOT.
- Windows, doors and openings · 39202934MSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED AT EXP#1 FIRE ESCAPE ACCESS FROM APARTMENT PARTIALLY OBSTRUCTED BY WINDOW MOUNTED AC UNITS., REPAIR
- Windows, doors and openings · 39202766MSection 28-301.1 / OATH code 102 · ATOI OBSERVED EXCESSIVE DEBRIS @ EXPO 3. CONSISTING OF AIR COMPRESSOR, LADDERS, SAW, OLD WINDOWS, SCREENS AND A STEEL WINDOW GATE.
- Windows, doors and openings · 39202932ZSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED FIRE ESCAPE ACCESS FROM APARTMENTS AT FRONT OF THE BUILDING PARTIALLY OBSTRUCTED BY WINDOW MOUNTED
- Roof and weather protection · 39202720RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT 1ST FLR COMMON HALLWAY - 1. CEILING OPENING OBSERVED APPRX 4' X 4
- Masonry or façade deterioration · 39202477XSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. AT TIME OF INSPECTION, OBSERVED APPROX. 4' HIGH MASONRY RETAINING WALL WI
- Roof and weather protection · 39202859LSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED MULTIPLE MISSING STAIR SPINDLES, STAIRCASE PITCHED, LOOSE/HANGING SHEETROCK THROUGHOUT TWO FLOORS,
- Roof and weather protection · 39202738PSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED STAIR CASE FROM 4 FLOOR TO ROOF LEVEL STRINGER DISLODGED, TREAD DISPLACED AND STAIRCASE IN DANGER T
- Masonry or façade deterioration · 39194541YSection 28-301.1 / OATH code 102 · DISREPAIR AT ALL PARAPETS LEVEL AND EXPOSURE'S #4 FACADE. BRICKS ARE MISSING/DELAMINATING/SEPARATING WITH MORTAR MISSING ALL THROU
- Windows, doors and openings · 39202839YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ATOI I OBSERVED AT FRONT CEILING/ROOF LEVEL ,PIECES OF SOFFIT FALLING APART
- Windows, doors and openings · 39202933KSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED AT EXP#1 FIRE ESCAPE ACCESS FROM 2ND FLOOR APT. PARTIALLY OBSTRUCTED BY WINDOW MOUNTED AC UNIT. ALS
- Fire prevention or detection system · 39202776XSection 28-301.1 / OATH code 102 · AT THE TIME OF INSPECTION OBSERVED THROUGH OUT THE BUILDING PAINTED SPRINKLER CAPS, MISSING CAPS & PAINTED SPRINKLER HEADS WHICH I
- Plumbing fixture and drainage configuration · 39202774MSection 28-301.1 / OATH code 102 · AT THE TIME OF INSPECTION OBSERVED THE HOT WATER HEATERS IN THE MAIN HOT WATER HEATER ROOM ON THE ROOF INSTALLED WITH PVC PIPING O
- Masonry or façade deterioration · 39202929HSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION, INSPECTOR OBSERVED MULTIPLE CRACKS AT EXP 1. ALSO OBSERVED DAMAGE TO GARAGE AREA WALL/OPENING, REPAIR AND/R
- Windows, doors and openings · 35718654JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. PROPERTY IS AN ATTACHED 3+C MIXED USE DWELLING LOCATED ON A CORNER LOT. O
- Zoning, site use or regulated sign · 39203002RSection 28-301.1 / OATH code 102 · ATOI OBSERVED A FAILURE TO MAINTAIN, WITH EXCESSIVE CONSTRUCTION DEBRIS PILED UP AT THE FRONT YARD. THIS CREATES A HAZARDOUS CONDI
- Masonry or façade deterioration · 35733187PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. I OBSERVED HAZARDOUS CONDITIONS AT FRONT ELEVATION/EXPOSURE ONE OF THE BUIL
- Authorized use versus observed occupancy · 39202878RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED IN THE BASEMENT IN THE MAIN SERVICE SW FOR THE BUILDING POWER IS B
- Wall / exterior structural condition · 39202258XSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER NOTED; RETAINING WALL AT REAR YARD EXP (3) OF PREMISES IS LEANING DUE TO THE
- Windows, doors and openings · 39202935YSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED AT EXP#1 FIRE ESCAPE ACCESS FROM APARTMENT AT MULTIPLE LOCATIONS PARTIALLY OBSTRUCTED BY WINDOW MOU
- Safe building maintenance · 39203224MSection 28-301.1 / OATH code 102 · NOTICED SECTION OF CORNICE COLLPAPSED AND HANGING EXP 1/2 FRONT OVER A BUS STOP. FDNY CALLED TO IMMEDIATELY REMOVE CORNICE. STAE O
- Construction fencing or site enclosure · 39203076JSection 28-301.1 / OATH code 102 · NOTED THERE ARE PORTIONS OF ROOFING MATERIAL & GUTTER (TROUGH) THAT HAVE BECOME DISLODGED. CHAIN LINK FENCING IS NOT SECURED AND P
- Roof and weather protection · 35728239LSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AS NOTED: AT TIME OF INSPECTION OBSERVED AT SITE A DEFECTIVE ROOF WITH BROK
- Fire prevention or detection system · 39203142ZSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION, OBSERVED SPRINKLERS IN THE STORAGE ROOM OBSTRUCTED AGAINST THE WALL EFFECTING THE SPRAY REACH, CONTRARY TO
- Elevator safety and service status · 35721881RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN. OBSERVED ELEVATOR D12 MALFUNTIONED TRAPPING GUESTWHICH LEAD TO FDNT RESCUE INDIVIDUALS FROM ELEVATOR ON THE 4
- Masonry or façade deterioration · 39191759NSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT THE TIME OF INSPECTION OBSERVED AT EXPOSURE #1 MORTAR MISSING BET
- Masonry or façade deterioration · 39202280MSection 28-301.1 / OATH code 102 · NOTED SOME VERTICAL AND HORIZONTAL CRACKS FIXED AT EXPOSURE #4. CRACKS STILL NOT REPAIRED AT EXPOSURE #1 AND CORNER EXP. 1 & 4., R
- Safe building maintenance · 39203227HSection 28-301.1 / OATH code 102 · NOTED COAL SHOOT COVER CONNECTED TO BUILDING DEFORMED AND IN DISREPAIR. UNEVEN COVER PRESENTS A TRIPPING HAZARD TO PEDESTRIANS., R
- Masonry or façade deterioration · 35728238JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AS NOTED: AT TIME OF INSPECTION OBSERVED VERTICAL CRACK EXTENDING UP TO PAR
- Masonry or façade deterioration · 35722053XSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED AT EXPO 1 AND 2(FRONT AND LEFT) STOOP 1ST FL
- Masonry or façade deterioration · 39202842PSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED MANY VERTICAL CRACKS ON FACADE WALL AT EXPOSURE # 3 AND # 4 ALSO VIOLATION #39055330Y ISSUED ON 02-
- Zoning, site use or regulated sign · 39203135KSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION - RAZOR BARBED WIRE WAS OBSERVED ATTACHED TO T
- Masonry or façade deterioration · 39203102YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION - GLASS PANE AT FRONT ENTRY DOOR WAS OBSERVED
- Windows, doors and openings · 39193495HSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION, OBSERVED AT INTERIOR OF APT 4A, LIVING ROOM AND BEDROOM FLOORS ARE SLOPING WITH LARGE GAP BETWEEN FLOOR AND
- Fire prevention or detection system · 39203220PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN. AT 2ND FLOOR THE SPRINKLER HEADS WERE PAINTED OVER ALONG WITH FOREIGN OBJECT BLOCKING SPRINKLER HEADS., REPAI
- Authorized use versus observed occupancy · 39203216MSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN. AT CELLAR LEVEL CEILING IS IN A STATE OF DISREPAIR WITH DAMAGE AND OR MISSING SECTIONS ALONG WITH MISSING AND
- Masonry or façade deterioration · 39203228JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION OF A 3 STORY BUILDING OBSERVED STEP CRACKS AT EXP 1,
- Authorized use versus observed occupancy · 39203204PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE- COMPLIANT MANNER. NOTED 6- 20 LBS ( EACH) PROPANE TANKS STORED AT EXP.#3 BY THE CELLAR EXIT
- Zoning, site use or regulated sign · 39203223KSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING SIGN AT BUILDING EXTERIOR. AT TIME OF INSPECTION, OBSERVED SIGN ASSOCIATED WITH COMMERCIAL ESTABLISHM