Examples under OATH infraction code 151
202 distinct enforcement-description examples carrying this infraction code. Check the actual summons before interpreting the code.
- Elevator safety and service status · 39204210XSection 28-301.1 / OATH code 151 · CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSP
- Elevator device maintenance and safety devices · 39203929MSection 28-301.1 / OATH code 151 · CLASS 1 (CU):FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER PASSENGER ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INS
- Safe building maintenance · 39204081ZSection 28-301.1 / OATH code 151 · NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS A CONTROLLER
- Safe building maintenance · 39204095JSection 28-301.1 / OATH code 151 · FIREMAN SERVICE NOT CODE COMPLIANT. REMEDY: UPDATE AND REPLACE LOBBY KEY SWITCH AND IN CAR KEY SWITCH TO MEET THE MINIMUM STANDARD
- Elevator safety and service status · 39204279YSection 28-301.1 / OATH code 151 · RTS CLASS 1: FAILURE TO MAINTAIN THE ELEVATOR IN A CODE-COMPLIANT MANNER. UPON INSPECTION, THE DEVICE WAS FOUND OUT OF SERVICE, CR
- Elevator device maintenance and safety devices · 39204327JSection 28-301.1 / OATH code 151 · CEASE USE ORDER: ALARM BELL AND IN-CAR EMERGENCY COMMUNICATION ARE INOPERATIVE. ELEVATOR DOES NOT SERVICE THE TOP FLOOR. CLASS 2 I
- Elevator safety and service status · 39203849MSection 28-301.1 / OATH code 151 · CEASE USE ORDER: UNPROTECTED OPENING IN THE CAR ENCLOSURE ABOVE THE COP OPENS DIRECTLY INTO THE HOISTWAY. CLASS 2 ITEMS: KEY-SWITC
- Elevator safety and service status · 39204153ZSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR IN BUILDING CODE COMPLIANT AS PER BC3001.2 & 27-987. UPON AN INSPECTION THE ELEVATOR IS FOUND TO BE O
- Elevator safety and service status · 39202972NSection 28-301.1 / OATH code 151 · CLASS 1 RESTORE TO SERVICE: ELEVATOR REMAINS OUT OF SERVICE AT THE TIME OF REINSPECTION. PREVIOUSLY CITED CONDITION REMAINS UNCORR
- Elevator safety and service status · 39202456RSection 28-301.1 / OATH code 151 · VF... R T S... 97-X-17..... ELEVATOR IN BUILDING OUT OF SERVICE , UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATIN
- Safe building maintenance · 39204391YSection 28-301.1 / OATH code 151 · (CEASE USE) DEFECTIVE ZONE RESTRICTOR.
- Elevator safety and service status · 39204408LSection 28-301.1 / OATH code 151 · CLASS 1 (CU):FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER PASSENGER ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INS
- Elevator safety and service status · 39204209ZSection 28-301.1 / OATH code 151 · 1) THE ENTIRE DOOR OPERATOR IS MALFUNCTIONING. THIS CAUSING THE ELEVATOR TO HAVE DLM FAULTS. REPAIR/REPLACE THE DOOR OPERATOR AND
- Elevator safety and service status · 39204586YSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR EQUIPMENT AS PER BC 3001.2 & 27-987 UPON AN INSPECTION THE ELEVATOR IS FOUND TO BE OUT OF SERVICE CRE
- Elevator device maintenance and safety devices · 39202672LSection 28-301.1 / OATH code 151 · CEASE USE ITEM:CEASE USE: DOOR RESTRICTOR INOPERATIVE. IN VIOLATION OF ASME A17.1-2013 2.14.5.7 AND 2.14.4.2. CONDITION EXPOSES TH
- Elevator safety and service status · 39202296RSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR IN CODE COMPLIANT AS PER BC3001.2 & 27-987. CLASS 1: CEASE USE. MACHINE/SHEAVE IS PRODUCING ABNORMAL
- Elevator device maintenance and safety devices · 39204122XSection 28-301.1 / OATH code 151 · 1) THE DOOR ZONE RESTRICTOR PLUNGER IS MISSING (RC SUMMON#39148835M)(CU)(8.11.1.5). 2) THE CAT-1 TAG AND THE FIRE EXTINGUISHER TAG
- Elevator safety and service status · 39204628NSection 28-301.1 / OATH code 151 · CLASS 1 (CU):FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER PASSENGER ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INS
- Elevator device maintenance and safety devices · 39204398RSection 28-301.1 / OATH code 151 · ROPE GRIPPER NOT WORKING. C/U. (5.11.17.1)REPAIR. PI IN LOBBY NOT WORKING.(2.27.11.4) REPAIR. CLEAN CAR TOP AND DOOR EQUIPMENT.
- Elevator device maintenance and safety devices · 39204763XSection 28-301.1 / OATH code 151 · CLASS 1: FIREFIGHTER'S SERVICE PHASE I & PHASE II - 1620 KEY ROTATES FREELY WITHOUT DISTINCT POSITIONS, INDICATING IMPROPER FIRE S
- Safe building maintenance · 39196517NSection 28-301.1 / OATH code 151 · 100/L/10 CAR CEASE USE , CLASS 1, DLM IS NOT WORKING DEFECTIVE REPAIR,40/P/7 MACHINE ROOM NO ACCESS PROVIDE.
- Elevator device maintenance and safety devices · 39195825KSection 28-301.1 / OATH code 151 · 1) BRAKE TAG IS EXPIRED (8.11.1.6) 2) AN ELEVATOR IN SECTION OF BUILDING OR BUILDING IS OUT-OF-SERVICE. UPON INSPECTION THE DEVICE
- Zoning, site use or regulated sign · 39196559LSection 28-301.1 / OATH code 151 · CLASS 1 ITEM: INOPERATIVE DISC BRAKE MONITOR (2.24.8.) CLASS 2 ITEM : UNREADABLE CONTROLLER FUSES (NEC 620). REMOVE DECEASED ANIMA
- Elevator device maintenance and safety devices · 39197940PSection 28-301.1 / OATH code 151 · CLASS 1(CU): FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER PASSENGER ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INS
- Elevator safety and service status · 39196881JSection 28-301.1 / OATH code 151 · CLASSS 1 ITEM: RTS CLASS 1: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27
- Elevator safety and service status · 39179523PSection 28-301.1 / OATH code 151 · RTS CLASS 1: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER AS PER BC3001.2 & 27-987 .UPON AN INSPECTION THE ELEVATOR WAS F
- Elevator safety and service status · 39171640HSection 28-301.1 / OATH code 151 · CLASS 1: LOBBY FIREMAN SERVICE KEY SWITCH INOPERATIVE (PHASE I) - KEY CYLINDER ROTATES 360 - NO ELEVATOR RECALL. THIS IS A SAFETY
- Elevator safety and service status · 39179522NSection 28-301.1 / OATH code 151 · RTS CLASS 2: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANCE AS PER BC3001.2 & 27-987. UPON AN INSPECTION THE ELEVATOR WAS FOUND O
- Elevator device maintenance and safety devices · 39198049KSection 28-301.1 / OATH code 151 · CEASE USE ITEM CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE, CREATING A HAZARDOUS CONDITION PER 1RCNY11-02. REMEDY: RESTORE TO
- Elevator safety and service status · 39132102ZSection 28-301.1 / OATH code 151 · RESPONDING TO A 311 ELEVATOR, COMPLAINT, UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT -OF -SERVICE,. AS PER 1RCNY 11-02. THIS DE
- Elevator device maintenance and safety devices · 39199994JSection 28-301.1 / OATH code 151 · CLASS 1 AGG 1: FIREFIGHTER'S SERVICE PHASE I DOES NOT RECALL THIS DEVICE TO THE MAIN FLOOR AS REQUIRED. AS PER ASME A17.1 2.27. TH
- Elevator safety and service status · 39197032JSection 28-301.1 / OATH code 151 · CLASS 1:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER PASSENGER ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTI
- Safe building maintenance · 39180776LSection 28-301.1 / OATH code 151 · EMERGENCY IN CAR OUTSIDE COMM INOPERATIVE , REPAIR / DLM INOPERATIVE , REPAIR
- Structural and interior building component · 39141262MSection 28-301.1 / OATH code 151 · CLASS 1: 4TH FLOOR HOIST DOOR HAS DAMAGED KEEPER. REPLACE KEEPER AND RESTORE SERVICE TO FLOOR. CLASS 2: CAR BUTTON STATION NOT TAG
- Safe building maintenance · 39148412KSection 28-301.1 / OATH code 151 · CEASE USE ITEM: MISALIGNED ZONE LOCK RESTRICTOR. PLUNGER DOES NOT GRAB OPERATOR WHEEL. CLASS 2 ITEM: MISALIGNED CAB MIRROR. INOPER
- Elevator safety and service status · 39100337RSection 28-301.1 / OATH code 151 · RESPONDING TO A 311 ELEVATOR COMPLAINT, UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT-OF-SERVICE AS PER 1RCNY 11-02, THIS DEVICE
- Elevator safety and service status · 39172902NSection 28-301.1 / OATH code 151 · : THE ONLY ELEVATOR IN BUILDING OUT OR SERVIVE . UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A HAZARDOUS CON
- Elevator device maintenance and safety devices · 39199082RSection 28-301.1 / OATH code 151 · CEASE USE ITEM: ELEVATOR DOOR ZONE RESTRICTOR INOPERATIVE. AS PER (ASME A17.1-2013 / NYC APPENDIX K 2.26.1.40.1 AND 8.6.4.19). REM
- Elevator safety and service status · 39196913PSection 28-301.1 / OATH code 151 · ELEVATOR REMAINS OUT OF SERVICE FOR AN EXTENDED PERIOD AND HAS NOT BEEN RESTORED TO OPERATION. PREVIOUSLY CITED CONDITION REMAINS
- Elevator device maintenance and safety devices · 39164347NSection 28-301.1 / OATH code 151 · CLASS 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO REST
- Safe building maintenance · 39164510YSection 28-301.1 / OATH code 151 · CEASE USE ITEMS: BYPASSED PLANK SWITCH. 2) BUILDUP ON TENSION SHEAVE CAUSING SLACK IN GOVERNOR ROPE. CLASS 2 ITEMS: ROUGE DEVELOPI
- Safe building maintenance · 39180138RSection 28-301.1 / OATH code 151 · RESPONDING TO A 311 COMPLAINT, UPON DEVICEIS FOUND THAT THE DOOR RESTICTOR WAS NOT WORKING CEASE USE THE DEVICE REMEDY REPAIR AND
- Safe building maintenance · 39164859RSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER, UPON A INSPECTION THE 3RD DOOR SHAFT WAY DOOR FOUND SLAMING AS IT CLOSE, TH
- Elevator device maintenance and safety devices · 39135517YSection 28-301.1 / OATH code 151 · CEASE USE ITEMS: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. DOOR LOCK MONITORING I
- Elevator device maintenance and safety devices · 39204311PSection 28-301.1 / OATH code 151 · CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE (ASME A17.1-2013 / NYC APPENDIX K 2.26.1.40.1, 8.6.4.19). REMEDY: CORRECT AND EMA
- Safe building maintenance · 39166173LSection 28-301.1 / OATH code 151 · UPON REINSPECTION, THE DEVICE IS FOUND TO BE OUT OF ORDER, BY THE COMMISSIONER ORDER, REMEDY REPAIR CEASE USE ITEMS, THEN CONTACT
- Elevator safety and service status · 39182172JSection 28-301.1 / OATH code 151 · RTS CLASS 1: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. REM
- Safe building maintenance · 39155345PSection 28-301.1 / OATH code 151 · CEASE USE ITEM: INOPERATIVE DOOR LOCK MONITORING AS REQUIRED BY CODE AT TIME OF INSTALLATION. CLASS 2 ITEMS: REPALCE WORN GIBS WHE
- Elevator safety and service status · 39175028JSection 28-301.1 / OATH code 151 · VF... R T S... ELEVATOR IN BUILDING OUT OF SEVICE UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE . REPAIR AND RESTORE TO
- Elevator safety and service status · 39182078NSection 28-301.1 / OATH code 151 · UPON INSPECTION FOUND THAT THE BUILDING ONLY ELEVATOR HAS BEEN OUT OF SERVICE FOR PERIOD OF SEVERAL MONTHS THE BUILDING CONSISTS O
- Safe building maintenance · 39175635LSection 28-301.1 / OATH code 151 · 97 / X/17 CLASS 1 RESTORE TO SERVICE FOR PROPER INSPECTION BY DOB.
- Elevator device maintenance and safety devices · 38270430RSection 28-301.1 / OATH code 151 · CU05A10; 37Q03; 25M07; 16B10; 39B09; 68B07; 37T07; 100M07. CEASE USE` 05-DOOR ZONE RESTRICTOR HAS BEEN ALTERED AND RENDERED INOPER
- Safe building maintenance · 39153074NSection 28-301.1 / OATH code 151 · UPON RE-INSECTION OF THE DEVICE IS NOT RESTORED TO SERVICE RUCURING CONDITION. REMEDY: REPAIR DEVICE THEN CONTACTNYCDOB FOR RE-INS
- Elevator device maintenance and safety devices · 39118324NSection 28-301.1 / OATH code 151 · CLASS 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR BYPASSED. CLASS 2 ITEMS: IN-CAR COMMUNICATION INOPERATIVE. IN-CAR EXHAUST FAN INOPERA
- Elevator safety and service status · 39201678HSection 28-301.1 / OATH code 151 · CLASS 1:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER PASSENGER ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTI
- Elevator device maintenance and safety devices · 39202014JSection 28-301.1 / OATH code 151 · CEASE USE ITEMS: (1) IN CAR EMERGENCY STOP SWITCH INOPERATIVE ASME A17.1 2.26.2. (2) : DOOR ZONE RESTRICTOR INOPERATIVE, CREATING
- Elevator safety and service status · 39201858PSection 28-301.1 / OATH code 151 · 97-X-17 THE ELEVATOR IN BUILDING OUT OF SERVICE UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A HAZARDOUS COND
- Elevator safety and service status · 39202094ZSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR EQUIPMENT AS PER BC3001.2 & 28-987. RTS CLASS 1: UPON AN INSPECTION THE ELEVATOR IS FOUND TO BE OUT O
- Safe building maintenance · 39202028KSection 28-301.1 / OATH code 151 · CEASE USE ITEMS: 1) NON WORKING DLM (A17.3 3.10.12.). BY PASSED PLANK SWITCH (2.18). 3) EXCESSIVE GAP BETWEEN RIGHT BRAKE PAD AND
- Elevator safety and service status · 39202048HSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR ASPER BC3001.2 & 27-987. UPON AN INSPECTION THE ELEVATOR IS FOUND OUT OF SERVICE CREATING A HAZARDOUS
- Elevator device maintenance and safety devices · 39202288RSection 28-301.1 / OATH code 151 · CLASS 1 C/U: 1. DOOR ZONE RESTRICTOR - DOOR ZONE RESTRICTOR INOPERATIVE, FAILING REQUIRED PREVENTION OF DOOR OPENING OUTSIDE THE D
- Elevator device maintenance and safety devices · 39202177YSection 28-301.1 / OATH code 151 · VF... CEASE USED... DOOR RESTRICTOR NOT WORKING ..DOOR ZONE RESTRICTOR HAS BEEN TEMPERED WITH DISABLED INOPREATIVE . THIS ISASAFET
- Elevator device maintenance and safety devices · 39202289ZSection 28-301.1 / OATH code 151 · CLASS 1 C/U: 1. BRAKE SWITCH MONITOR - BRAKE SWITCHES MONITOR INACTIVE, FAILING REQUIRED ELECTRICAL MONITORING OF BRAKE STATUS AS
- Elevator safety and service status · 39202093RSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN DEVICE IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE ONL
- Elevator device maintenance and safety devices · 39202152HSection 28-301.1 / OATH code 151 · CLASS 1 ITEM: LOBBY FLOOR HOISTWAY DOOR CLOSER ARM NOT PROPERLY SECURED; SECURE AS REQUIRED, ASME A17.1 2.11.3. CLASS 2 ITEMS: SUP
- Elevator safety and service status · 39202146LSection 28-301.1 / OATH code 151 · RTS CLASS 1: FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS REQUIRED BY NYC BUILDING CODE
- Elevator safety and service status · 39202840LSection 28-301.1 / OATH code 151 · CLASS 1 RTS ELEVATOR REMAINS OUT OF SERVICE FOR AN EXTENDED PERIOD AND HAS NOT BEEN RESTORED TO OPERATION. PREVIOUSLY CITED CONDIT
- Elevator device maintenance and safety devices · 39202287PSection 28-301.1 / OATH code 151 · CLASS 1 C/U: 1. DOOR LOCK MONITOR - DOOR LOCK MONITOR INOPERATIVE, FAILING REQUIRED ELECTRICAL VERIFICATION OF HOISTWAY DOOR LOCKS
- Elevator safety and service status · 39202012XSection 28-301.1 / OATH code 151 · CLASS 1 RTS:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPE
- Elevator device maintenance and safety devices · 39202290XSection 28-301.1 / OATH code 151 · CLASS 1 C/U: 1. BRAKE SWITCH MONITOR - BRAKE SWITCHES MONITOR INOPERATIVE, FAILING REQUIRED ELECTRICAL MONITORING OF BRAKE STATUS
- Elevator safety and service status · 39202032NSection 28-301.1 / OATH code 151 · VF.... R T S... 97-X 17...ELEVATOR IN BUILDING OUT OF SERVICE , UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING
- Elevator device maintenance and safety devices · 39202303XSection 28-301.1 / OATH code 151 · CEASE USE ITEM: FUSE BYPASSED WITH COPPER WIRE, DEFEATING REQUIRED ELECTRICAL PROTECTION, IN VIOLATION OF ASME A17.1-2013 2.26.1.5
- Safe building maintenance · 39202102JSection 28-301.1 / OATH code 151 · THE CAT-1 TAG IS MISSING (8.11.1.6). 2) THE ZONE LOCK RESTRICTOR WAS IN THE OFF POSITION (RC)(8.11.1.5). 3) THE PHONE IS STILL NOT
- Elevator safety and service status · 39201864LSection 28-301.1 / OATH code 151 · CLASS 1RTS:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECT
- Structural and interior building component · 39202137JSection 28-301.1 / OATH code 151 · 1) THIS DEVICE IS SKIPPING FLOORS (8.11.2.1.1)(CU) 2) THIS DEVICE IS MOVING VERY SLOW (8.11.2.1.3)(CU).
- Elevator device maintenance and safety devices · 39202231XSection 28-301.1 / OATH code 151 · CEASE USE ITEM:DOOR ZONE RESTRICTOR DEVICE HAS BEEN INTENTIONALLY BYPASSED. THE RESTRICTOR PLUNGER WAS OBSERVED DEFEATED, ALLOWING
- Elevator safety and service status · 39202098XSection 28-301.1 / OATH code 151 · VF... R T S 97-X-17.... ELEVATOR IN BUILDING OUT OF SERVICE , UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A
- Safe building maintenance · 39186632JSection 28-301.1 / OATH code 151 · UPON INSPECTION OF A SINGLE CAR BUILDING AT THE REAR OF LOT DEVICE IS FOUND TO BE OUT OF SERVICE, DEVICE PROVIDE SERVICE IN A 6 ST
- Elevator safety and service status · 39202238ZSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. AS PER NYC BUILD
- Elevator safety and service status · 39176912PSection 28-301.1 / OATH code 151 · CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSP