Cases associated with NYC DOB 28-105.12.2
137 distinct descriptions associated with this law label in the October 2026 enforcement extract. These are source allegations with educational draft analyses, not verified outcomes.
- Demolition, structural removal or excavation · 39558355PSection 28-105.12.2 / OATH code 182 · AT TIME OF INSPECTION, OBSERVED BUILDINGS B AND C HAD BEEN FULLY DEMOLISHED WHILE BUILDING A REMAINED, CONTRARY TO THE APPROVED DE
- Sidewalk shed and public protection · 39558290NSection 28-105.12.2 / OATH code 182 · BC 3307.4.7 TEMPORARY PUBLIC WALKWAY: I OBSERVED AT THE STORAGE WORK ZONE AREA WITH A SIDEWALK SHED IN PLACE WAS MISSING THE REQUI
- Structural and interior building component · 39201834KSection 28-105.12.2 / OATH code 282 · OBSERVED THE NEWLY INSTALLED STEEL BEAM CONNECTION TO THE NEW & EXISTING FOUNDATION WALL IS NOT BOLTED AND WAS SHIMMED UP WITH PIE
- Electrical installation and permit · 39558427PSection 28-105.12.2 / OATH code 282 · OBSERVED A CONSTRUCTION FENCE WITH AN MAKESHIFT PLATFORM INSTALLED ON TOP OF THE FENCE, EXTENDING OVER TO A GENERATOR LOCATED OUTS
- Zoning, site use or regulated sign · 39558387JSection 28-105.12.2 / OATH code 282 · OBSERVED: FENCE ERECTED AROUND THE SITE. UPON REVIEW OF APPROVED DRAWINGS, IT WAS NOTED THAT THE GATE/GARAGE DOORS WERE DESIGNED T
- Authorized use versus observed occupancy · 39558377XSection 28-105.12.2 / OATH code 182 · AT TIME OF INSPECTION OBSERVED STRUCTURAL WORK STEAL BEAM IN PLACE AT CELLAR LEVEL SUPPORTING FIRST FLOOR. STAIRS ARE INSTALLED ON
- Demolition, structural removal or excavation · 39558436RSection 28-105.12.2 / OATH code 182 · OBS. ACTIVE EXCAVATION AT BOTH LOT LINES CONTRARY TO APPROVED SOE. REQ'D PERIMETER SOE PER B-E/SOE-202 NOT INSTALLED AS EXCAVATION
- Roof and weather protection · 39544628YSection 28-105.12.2 / OATH code 282 · PROPOSED 16 STORY NEW BUILDING ACTIVE SITE. CONCRETE POURING AT 11 FL.ROOF PROTECTION INSTALLED CONTRARY TO SSP DETAILS PG SSP 119
- Scaffold platform and fall protection · 39544629XSection 28-105.12.2 / OATH code 282 · 16 STORY NEW BUILDING ACTIVE SITE.CONCRETE POURING AT 11 FL. SUPPORTED SCAFFOLD 110 FT IN HEIGHT IN PLACE AT ALL EXPOSURES.SCAFFOL
- Demolition, structural removal or excavation · 39558351HSection 28-105.12.2 / OATH code 282 · AT INSPECTION OF A PROPOSED 2-STORY BUILDING IN EXCAVATION, EXP# 2 WAS OBSERVED WITH A 10-FT-DEEP EXCAVATION LACKING REQUIRED PILI
- Authorized use versus observed occupancy · 39201818KSection 28-105.12.2 / OATH code 282 · WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS. ATOI OBSERVED PERMITS FOR RENOVATION OF APART
- Authorized use versus observed occupancy · 39558463MSection 28-105.12.2 / OATH code 182 · Q01424052.@PERMITTED&ACTIVE SITE OBSERVE WORK NOT CONFORM TO PLANS COMPROMISING STRUCTURAL STABILITY&AFFECTING HEALTH&LIFE SAFETY
- Demolition, structural removal or excavation · 39558478PSection 28-105.12.2 / OATH code 182 · OBS. 1-SIDED FNDN WALL FORM/SHORING NONCONFORMING TO RDP DETAIL 16/FW-005. STEEL-PIPE/TIMBER BRACES ENDED LOOSE ON SLAB/WOOD; NEIT
- Traffic barriers and worksite separation · 39558363PSection 28-105.12.2 / OATH code 282 · OBSERVED STREET OPERATIONS AT EXP#1 WITH UNPROTECTED TREE MATERIALS STORED ON STREET WITHOUT ANY BARRIERS CONTRARY TO SITE SAFETY
- Demolition, structural removal or excavation · 39558375MSection 28-105.12.2 / OATH code 282 · DURING MY INSPECTION OF A NEW MULTI-STORY NB AT THE SOE PHASED. I OBSERVED CHANGES NOT REFLECTING THE APPROVED DOB SOE / FOUNDATIO
- Departure from approved construction documents · 39558396LSection 28-105.12.2 / OATH code 182 · DURING THE INSPECTION OF A 9STORY NB AT AN ACTIVE JOB SITE, IT WAS OBSERVED THAT TIMBER SOLDIER POSTS WITH 3 INCH TIMBER LAGGING,
- Windows, doors and openings · 39201691MSection 28-105.12.2 / OATH code 282 · WORK DOES NOT CONFORM TO PLANS. AT TIME OF INSPECTION, APPROVED DOB ENERGY AND ARCHITECTURAL DRAWINGS FOR WINDOW M6 TO HAVE A U-VA
- Authorized use versus observed occupancy · 39558412MSection 28-105.12.2 / OATH code 182 · AT TIME OF INSPECTION OF 6 STORY MIXED USE BUILDING OBSERVED WORK BEYOND APPROVED PLANS WITH COMPLETE GUT RENOVATION (FLOORS, WALL
- Demolition, structural removal or excavation · 39558511HSection 28-105.12.2 / OATH code 182 · AT TIME OF INSPECTION I OBSERVED EXCAVATION BEING CONDUCTED. UPON REVIEW OF DOB APPROVED PLANS WORK DOES NOT CONFORM TO APPROVED P
- Scaffold platform and fall protection · 39558472YSection 28-105.12.2 / OATH code 282 · OBSERVED SUSPENDED SCAFFOLD INSTALLED AND IN USE AT EXP#1,2,3-UPON CHECKING APPROVED PLANS FOR INSTALLATION OF TIEBACKS/LIFELINES-
- Demolition, structural removal or excavation · 39558515PSection 28-105.12.2 / OATH code 182 · AT THE TIME OF MY INSPECTION OBSERVED ACTIVE SITE WITH REMOVAL/ NEWLY INSTALLED WOOD JOISTS @ FLOORS 1,2,3,&4. UPON REQUEST NO TEM
- Sidewalk shed and public protection · 39558470KSection 28-105.12.2 / OATH code 282 · AT THE TIME OF MY INSPECTION I OBSERVED STORAGE/WORK ZONE AT EXP#1 ,OBSERVED CHUTE INSTALLED FROM SIDEWALK SHED TO STREET EXP#1-UP
- Departure from approved construction documents · 39202157RSection 28-105.12.2 / OATH code 282 · WORK DOES NOT CONFORM TO PLANS. AT TIME OF INSPECTION, APPROVED DOB ENERGY AND ARCHITECTURAL DRAWINGS FOR WALL TYPE WA1 TO HAVE A
- Demolition, structural removal or excavation · 39558503HSection 28-105.12.2 / OATH code 282 · OBS.ACTIVE EXCAVATION/FNDN WORK. KOMATSU PC238USLC EXCAVATOR ADJ. TO PARK AVE SOE; SURCHARGE/LOCATION NOT SHOWN ON APPR. SOE DOCS.
- Permit validity timeline · 39202398HSection 28-105.12.2 / OATH code 182 · PERMIT #B01009942 EXPIRED 12/19/2025 ON FILE. HOWEVER, ATOI OBSERVED BALCONY ON 3RD FLOOR, EXPO.1, EXTENDED TO APRX. 10 FT X 9 FT,
- Scaffold platform and fall protection · 39558635JSection 28-105.12.2 / OATH code 182 · DURING THE INSPECTION OF THE ACTIVE 8-STORY NB, IT WAS OBSERVED THAT THE PIPE SCAFFOLD/ENGINEERED ENCLOSURE AT EXPOSURE 2 IS NOT I
- Structural and interior building component · 39202665NSection 28-105.12.2 / OATH code 182 · ATOI, OBSERVED 2-STORY BUILDING WITH ACTIVE PERMIT #B01357954-I1-GC. WORK OBSERVED DOES NOT CONFORM TO APPROVED PLANS, INCLUDING 1
- Structural and interior building component · 39202649NSection 28-105.12.2 / OATH code 182 · WORK DOES NOT CONFORM TO APPROVED CONST. DOC. AND/OR APPROVED AMENDMENTS. OBSERVED APPROVED DRAWINGS FOR JOB# M01360788-I1-SC HAS
- Demolition, structural removal or excavation · 39558566PSection 28-105.12.2 / OATH code 182 · OBSERVED: ACTIVE SITE UPON INSPECTION SAW EXCAVATION DONE FOR HORIZONTAL EXTENSION, REVIEW DRAWINGS PLANS FOUND: NO SOLDIER PILES
- Zoning, site use or regulated sign · 39202669KSection 28-105.12.2 / OATH code 182 · WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/ OR AMENDMENTS; NOTE JOB APPLICATION X01285374 SHOWS NO WORK TO BE DO
- Authorized use versus observed occupancy · 39202667RSection 28-105.12.2 / OATH code 182 · ATOI, OBSERVED 2-STORY BUILDING WITH ACTIVE PERMIT #B01357954-S1-PL. WORK OBSERVED DOES NOT CONFORM TO APPROVED PLANS, INCLUDING R
- Windows, doors and openings · 39202419HSection 28-105.12.2 / OATH code 282 · WORK DOES NOT CONFORM TO PLANS. AT TIME OF INSPECTION, APPROVED DOB ENERGY AND ARCHITECTURAL DRAWINGS CALL OUT CELLAR WINDOWS TO H
- Structural and interior building component · 35730888YSection 28-105.12.2 / OATH code 282 · WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS. AS NOTED AT THE TIME OF INSPECTION OF A PROPO
- Departure from approved construction documents · 39202414ZSection 28-105.12.2 / OATH code 282 · THE STICKERS ON ALL INSTALLED WIDOWS SHOW U-FACTOR 0.27 CONTRARY WITH THE APPROVED DOB EN DRAWING AND ARCHITECTURAL DRAWING THAT I
- Sidewalk shed and public protection · 39558576ZSection 28-105.12.2 / OATH code 282 · AT THE TIME OF INSPECTION ON AN ACTIVE JOB SITE, I OBSERVED SIDEWALK SHED AT EXPOSURE 1 AND WAS NOT CONFORM TO PLANS AS PER PLANS
- Scaffold platform and fall protection · 39558585KSection 28-105.12.2 / OATH code 282 · DURING INSPECTION OF THE 4-STORY DEMOLITION, OBSERVED PIPE SCAFFOLD AT EXPOSURE # 1. UPON CHECKING ON THE APPROVED PIPE SCAFFOLD D
- Wall / exterior structural condition · 39558570HSection 28-105.12.2 / OATH code 282 · OBSERVED ON THE 3RD FLOOR OF THE SITE. STEEL BEAMS INSTALLED THAT CONNECTS FROM THE EXTERIOR OF THE BUILDING TO THE PROPOSED WALK
- Wall / exterior structural condition · 39202853KSection 28-105.12.2 / OATH code 282 · THE R-VALUE OF THE INSTALLED EXTERIOR WALLS OUTBOARD INSULATION AT EXPOSURE #1 IS R-VALUE 5 WITH THICKNESS 1" CONTRARY WITH THE AP
- Demolition, structural removal or excavation · 39558722HSection 28-105.12.2 / OATH code 282 · AT TIME OF INSPECTION OBSERVED: EXCAVATION WORK CONTRARY TO APPROVED DRAWINGS. SOE-005.00. EXCAVATION EXCEEDS DEEPER MEETING FOUND
- Scaffold platform and fall protection · 39558795ZSection 28-105.12.2 / OATH code 182 · DURING THE INSPECTION OF THE ALTERATION TO THE 17 STORY BUILDING, OBSERVED SUSPENDED SCAFFOLDS @EXP#1 TIE BACKS WHERE ATTACHED TO
- Structural and interior building component · 39202836ZSection 28-105.12.2 / OATH code 182 · OBSERVED AN ADDITIONAL LEVEL ADDED WITH A BALCONEY AT EXP 3 SUGGESTING A 3RD FLOOR. WORK IS CONTRARY TO APPROVED PLANS AND BEYOND
- Sidewalk shed and public protection · 39558774JSection 28-105.12.2 / OATH code 282 · I OBSERVED SIDEWALK SHED AT EXP#1 INSTALLED CONTRARY TO PLANS-MISSING POSTS AT LEFT SIDE CORNER EXP#1/2-ADITIONAL POSTS INSTALLED
- Authorized use versus observed occupancy · 39558689PSection 28-105.12.2 / OATH code 182 · STRUCTURAL FRAMING WORK AND TEMPORARY SHORING CONTRARY TO APPROVED DRAWINGS. OBSSERVED AT BASEMENT LEVEL,DIGING ONE FEET CONTRARY
- Departure from approved construction documents · 39558657KSection 28-105.12.2 / OATH code 182 · OBSERVED: FENCE WORK CONTRARY TO APPROVED DOCUMENTS FENCE ,ON SITE ERECTED ONLY EXP2&4 FRONT SIDE ., CONTRARY TO DRAWINGS A001.00
- Departure from approved construction documents · 39558684XSection 28-105.12.2 / OATH code 282 · OBSERVATION: CFS MISSING CROSS BRACING, STRAPS & U CHANNELS, COLD FORM STEEL INTEGRITY CAN BE COMPROMISED WITHOUT ALL COMPONENTS I
- Scaffold platform and fall protection · 39558690MSection 28-105.12.2 / OATH code 282 · 26 STORY FACADE ALTERATION ACTIVE SITE. OBSERVED SUSPENDED SCAFFOLDS/TEMPORARY EQUIPMENT IN PLACE WITH MASONRY FRAMES UNDERNEATH &
- Sidewalk shed and public protection · 39558750PSection 28-105.12.2 / OATH code 282 · UPON REVIEW SITE SAFETY PLAN -PROTECTION CONTRARY TO SSP(ROOF/OVERHEAD PROTECTION) AT EXP#4-SSP PLAN INDICATE ALL ADJ PROPERTY TO
- Scaffold platform and fall protection · 39558693HSection 28-105.12.2 / OATH code 282 · 26 STORY ALT2 FACADE WORK ACTIVE SITE. WORK CONTRARY TO APPROVED OUTRIGGER PLANS ONSITE. OBSERVED SUSPENDED SCAFFOLD IN PLACE/USE
- Structural and interior building component · 39202942MSection 28-105.12.2 / OATH code 282 · ON EXPOSURE#1,2,3 AND 4 FROM 1ST FLOOR TO 2ND FLOOR WERE INSTALLED METAL STUDS CONTRARY TO ARCHITECTURAL DRAWING THAT INDICATE WOO
- Sidewalk shed and public protection · 39558662PSection 28-105.12.2 / OATH code 282 · OBSERVED SIDEWALK SHED INSTALLED AT EXP# 1 UNDER APPLICATION #B01409772-WITH LETTER OF INSTALLATION PROVIDED TO GC-CONTRARY TO PLA
- Scaffold platform and fall protection · 39555995JSection 28-105.12.2 / OATH code 282 · AT THE TIME OF INSPECTION OF A 6-STORY BUILDING WITH FACADES OPERATION, I OBSERVED AT ROOF LEVEL OUTRIGGER SUSPENDED SCAFFOLDING E
- Scaffold platform and fall protection · 39558745KSection 28-105.12.2 / OATH code 282 · OBSERVED SUPPORTED SCAFFOLDING INSTALLED AROUND EXTERIOR OF JOBSITE. AT EXPO 1 TRUST INSTALLED & PROTRUDING OUT OF THE SYSTEM, OUT
- Sidewalk shed and public protection · 39558775LSection 28-105.12.2 / OATH code 282 · UPON INSPECTION I OBSERVED A SIDEWALK SHED INSTALLED AT EXPOS 1 CONTRARY TO THE APPROVED DRAWINGS. APPROX. 17FT OPEN SPAN WAS NOT
- Demolition, structural removal or excavation · 39558611PSection 28-105.12.2 / OATH code 282 · OBSERVED SUPPORT OF EXCAVATION WORK CONTRARY TO PLANS-MISSING ANGLES ON SIDE OF PILES WHERE LAGGING CONNECTS WITH NO RECOMMENDED S
- Scaffold platform and fall protection · 39558767LSection 28-105.12.2 / OATH code 282 · I OBSERVED SUPPORTED SCAFFOLD BEING INSTALLED AT EXP#2/3-CONTRARY TO PLANS-AT EXP#2 FIRST ROW OF FRAMES USED(3'MASONRY FRAMES)-NOT
- Departure from approved construction documents · 39203120HSection 28-105.12.2 / OATH code 182 · WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENTS. ATOI, I OBSERVED AT EXP 1 A WOOD AWNING APPRO
- Scaffold platform and fall protection · 39558805NSection 28-105.12.2 / OATH code 182 · OBS. EXCESSIVE SCAFFOLD FRAMES, PIPES, LUMBER & MISC. MATERIAL STORED/STACKED ON SIDEWALK SHED DECK, CONTRARY TO APPROVED RDP PLAN