1,428 distinct descriptions associated with this law label in the October 2026 enforcement extract. These are source allegations with educational draft analyses, not verified outcomes.
- Structural and interior building component · 39202541LSection 28-301.1 / OATH code 251 · 1) THE DOOR OPERATOR CHAIN IS SLACK (8.11.2.1.1). 2) THE DOOR RESTRICTOR NEEDS ADJUSTMENT (THE LACK CAN GO UNDER THE ROLLER)(8.11.
- Elevator device maintenance and safety devices · 39203108PSection 28-301.1 / OATH code 251 · CLASS 2:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER PASSENGER ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTI
- Boiler device inspection and filing · 39203705NSection 28-301.1 / OATH code 102 · ATOI OBSERVED IN CELLAR OF ABOVE PREMISES A NEW HOT WATER HEATER .THE WALL TO BOILER ROOM WAS PARTIALLY REMOVED ALSO THE DUMBWAITE
- Elevator safety and service status · 39161479LSection 28-301.1 / OATH code 151 · THE ONLY ELEVATOR IN SECTION OF BUILDING OR BUILDING IS OUT-OF-SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT-OF-SERVICE C
- Elevator device maintenance and safety devices · 39203233YSection 28-301.1 / OATH code 251 · CLASS 2 ITEMS: CAR VENTILATION FAN IS INOPERATIVE AND DOES NOT PROVIDE REQUIRED VENTILATION, IN VIOLATION OF ASME A17.1-2013 2.14.
- Masonry or façade deterioration · 39148671PSection 28-301.1 / OATH code 102 · ATOI OBSERVED EXCESSIVE DEBRIS IN REAR OF YARD, GARBAGE BAGS, BRICKS AND DIRT BAGS PRESENT, REPAIR AND/REPLACE
- Authorized use versus observed occupancy · 39203535JSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. PREMISES IS A 6 STORY M/D PLASTER CEILING IN BEDROOM OF APARTMENT 205 IS
- Means of egress and exit protection · 39203478MSection 28-301.1 / OATH code 202 · NOTED AT TIME OF INSPECTION OBSERVED LOBBY HALLWAY PARTIALLY OBSTRUCTED BY MISCELLANEOUS ITEMS INCLUDING GARBAGE BAGS AND A CRATE
- Elevator safety and service status · 39203106LSection 28-301.1 / OATH code 151 · AN ELEVATOR IN SECTION OF BUILDING OR BUILDING IS OUT-OF-SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT-OF-SERVICE CREATIN
- Safe building maintenance · 39203592XSection 28-301.1 / OATH code 102 · ATOI OBSERVED THAT SIDEWALK IS SEVERELY DAMAGED AND DEFECTIVE, CREATING A SAFETY HAZARD FOR PEDESTRIANS AND RESULTING IN THE ACCUM
- Elevator device maintenance and safety devices · 39203521ZSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITH, PARTS REMOVED RENDERING IT INO
- Masonry or façade deterioration · 39203457NSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER FOR VIOLATION #39170386R. OBSERVED ENTRY ARCHWAY LEANING FORWARD WITH STEP C
- Elevator device maintenance and safety devices · 39203586JSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR IN BUILDING CODE COMPLIANT AS PER BC 3001.2 & 27-987. CEASE USE ITEM CLASS 1 VIOLATION: DOOR ZONE RES
- Safe building maintenance · 39137522HSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER NOTED: AT TIME OF INSPECTION OBSERVED HEAVY AMOUNT OF DEBRIS/GARBAGE AND H
- Elevator device maintenance and safety devices · 39203268YSection 28-301.1 / OATH code 251 · CLASS 2 ITEMS: ELEVATOR MACHINE ROOM DOOR DAMAGED AND NOT SELF-LOCKING; REPAIR OR REPLACE DOOR/LOCKING DEVICE TO PROVIDE A PROPERL
- Permit validity timeline · 39203426KSection 28-301.1 / OATH code 302 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLAINT MANNER. AT TIME OF INSPECTION, OBSERVED FRONT PORCH AND BUILDING MATERIAL AT EXP
- Safe building maintenance · 39203680XSection 28-301.1 / OATH code 102 · OBSERVED AT THE ENCLOSED OUTDOOR SEATING DINING AREA AT THE WEST 6ST SIDE A FUNCTIONING MUSHROOM KITCHEN EXHAUST EXITING FUMES. PO
- Safe building maintenance · 39149024NSection 28-301.1 / OATH code 302 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. OBSERVED SIDEWALK CURB AT FRONT OF PROPERTY (EXP-1) ILLEGALLY CUT SO THAT
- Elevator device maintenance and safety devices · 39203479YSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR IN BUILDING CODE COMPLIANT AS PER BC3001.2 & 27-987. CLASS 1 VIOLATIONS ; EMERGENCY COMMUNICATION DEV
- Elevator device maintenance and safety devices · 39203575YSection 28-301.1 / OATH code 151 · CEASE USE ITEM: ELEVATOR DOOR ZONE RESTRICTOR INOPERATIVE, AS PER ASME A17.1-2013 / NYC APPENDIX K 2.26.1.40.1 AND 8.6.4.19. CORRE
- Elevator safety and service status · 39202658PSection 28-301.1 / OATH code 251 · 1) ADJUST/CLEAN GOVERNOR MAKING SQUEAKING NOISE. (2) PROVIDE CURRENT ELEVATOR COMPANY LABEL ON MAINLINE DISCONNECT AND CONTROLLER.
- Elevator safety and service status · 39203625NSection 28-301.1 / OATH code 151 · R T S . 97-X -17 ....ELEVATOR IN BULDING OUT OF SERVICE , UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A HAZA
- Masonry or façade deterioration · 39161694YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. AT EXPOSURE 1, PARAPET LEVEL, THERE IS A DISLODGED STONE. ALSO, THERE ARE
- Elevator safety and service status · 39203155HSection 28-301.1 / OATH code 151 · VF.... R T S ... 97-X -17.... ELEVATOR IN BUILDING OUT OF SERVICE . UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREAT
- Zoning, site use or regulated sign · 39203365XSection 28-301.1 / OATH code 302 · NOTED SIDEWALK CURB AT EXPOSURE #4 ILLEGALLY CUT SO THAT A PORTION OF THE SIDEWALK IS LOWERED ENABLING A VEHICLE TO DRIVE ONTO AN
- Masonry or façade deterioration · 39203893JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING CODE COMPLIANT. NOTED: BUILDING IN SEVERE DISREPAIR WITH CRACKED CEMENT PARGING, DISPLACED METAL SHEE
- Masonry or façade deterioration · 39203297NSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED THAT LOOSE/BULGING BRICKS ON TOP FLOOR AND VIOLATION #39147861L ISSUED ON 05-13-2025 FOR FAILURE TO
- Masonry or façade deterioration · 39202886RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF REINSPECTION FOR VIO#35685820H .. OBSERVED AT EXP#4 COURT YARD .
- Boiler device inspection and filing · 39203546PSection 28-301.1 / OATH code 354 · IN BOILER ROOM@ROOF>HWH'S #3+#5 ARE NOT OPERATIONAL+RE CIRCULATOR+FLANGES ARE DEFECTIVE+IN CELLAR STORAGE ROOM THERE IS STORAGE UN
- Elevator safety and service status · 39203587LSection 28-301.1 / OATH code 151 · VF.. R T S... 97-X-17...ELEVATOR IN BUILDING OUT OF SERVICE . UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A
- Structural and interior building component · 39203753HSection 28-301.1 / OATH code 126 · ATOI OBSERVED IN THE FIRST FLOOR OF THE PROPERTY BEYOND THE LOBBY FOR THE LEFTMOST PANIC DOOR WITH ONLY ONE WAY TO OPEN INTO THE H
- Roof and weather protection · 39203896PSection 28-301.1 / OATH code 102 · PART OF ROOF FENCE HAS BROKEN OFF AND A SECTION WITH BARBED WIRE ON IT IS HANGING OVER FRONT COURT YARD., REPAIR AND/REPLACE
- Elevator device maintenance and safety devices · 39203513ZSection 28-301.1 / OATH code 151 · CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE, CREATING A HAZARDOUS CONDITION PER 1RCNY11-02. REMEDY: RESTORE TO SERVICE IMMEDI
- Fire prevention or detection system · 39203880KSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING FIRE SUPPRESSION SYSTEM IN A CODE COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED MULTIPLE SPRINKLER
- Plumbing fixture and drainage configuration · 39203841HSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN. NOTED: AT A 6 STORY MULTI DWELLING GAINED ACCESS TO APT B8 AND OBSERVED EXPOSED AND UNCAPPED WATER AND WASTE
- Boiler device inspection and filing · 39203503PSection 28-301.1 / OATH code 254 · B-254 FTM BOILER FOUND A SLAT/FIN MODEL #LDWO OIL FIRE CONSISTING OF SEVEN MODULES TO BE INOPERABLE. CORRECT ALL VIOLATING CONDITI
- Safe building maintenance · 39148672RSection 28-301.1 / OATH code 102 · ATOI OBSERVED IN REAR OF PROPERTY APPROX.9 EXPOSED AND UNCAPPED REBARS PROTRUDING FROM UNPERMITTED CMU STRUCTURE APPROX.10% COMPLE
- Means of egress and exit protection · 39203641NSection 28-301.1 / OATH code 202 · ATOI NO EVIDENCE TO SUBSTANTIATE COMPLAINT. VIOLATION ISSUED FOR OBSTRUCTED PASSAGEWAY AT COMMON CORRIDOR. PERSONEL BELONGINGS INC
- Elevator safety and service status · 39203602KSection 28-301.1 / OATH code 151 · CEASE USE ITEM:CEASE USE ITEM: ELEVATOR DOOR-ZONE RESTRICTOR MISSING/NOT PROVIDED. ELEVATOR IS EQUIPPED WITH DLM BUT DOES NOT HAVE
- Elevator device maintenance and safety devices · 39203568XSection 28-301.1 / OATH code 151 · CEASE USE ITEM: CEASE USE: DOOR RESTRICTOR INOPERATIVE. IN VIOLATION OF ASME A17.1-2013 2.14.5.7 AND 2.14.4.2. CONDITION EXPOSES T
- Roof and weather protection · 39203897RSection 28-301.1 / OATH code 102 · ROOF LEVEL SECTION OF FENCE IS HANGING OFF AT EXP 1 OVER COURT YARD., REPAIR AND/REPLACE
- Boiler device inspection and filing · 39203883XSection 28-301.1 / OATH code 139 · FAILURE TO MAINTAIN THE REQUIRED FIRE-RESISTANCE-RATED SEPARATION BETWEEN THE BOILER ROOM AND ELECTRICAL ROOM. OBSERVED MULTIPLE U
- Authorized use versus observed occupancy · 39203666JSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION - INTERIOR STAIRCASE BETWEEN CELLAR & 1ST FLR
- Means of egress and exit protection · 39202815JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ATOI FOR VIO#39186561L , OBSERVED AT EXP#1 AC UNITS STICKING OUT BLOCKIN
- Safe building maintenance · 39202096MSection 28-301.1 / OATH code 251 · UPON INSPECTION THE HYDRAUIC DEVICE WAS BOUNING ON THE WAY UP REMEDY; REPAIR
- Elevator safety and service status · 39203714PSection 28-301.1 / OATH code 151 · CLASS 1:FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER PASSENGER ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTI
- Plumbing fixture and drainage configuration · 39145372LSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. AT TIME OF INSPECTION, OBSERVED IMPROPER DRAINAGE SYSTEM AT REAR OF THE B
- Boiler device inspection and filing · 39124692HSection 28-301.1 / OATH code 254 · NEWYORKER CG-80 BOILER=NO FRESH AIR TO ENCLOSED BOILER+HWH'S+DUALVALVE NOT PIPED DOWN+WIRES EXPOSED+FRONT BOILER JACKET NOT IN PLA
- Plumbing fixture and drainage configuration · 39203702HSection 28-301.1 / OATH code 202 · ATOI OBSERVED (PVC) PLASTIC PIPING BEING USED FOR WASTE LINES FOR LAVATORY SINK, WASH BOX FOR WASHING MACHINE AND FOR HAIR WASHING
- Roof and weather protection · 39203891XSection 28-301.1 / OATH code 102 · THE ROOF HAS BECOME POROUS ALLOWING RAINWATER TO ENTER DAMAGING THE HALLWAY CEILINGS ON ALL FLOORS., REPAIR AND/REPLACE; COMPLY WI
- Structural and interior building component · 39203649HSection 28-301.1 / OATH code 202 · OBSERVED LARGE SECTIONS OF CEILINGS THAT ARE MISSING AND PARTIALLY COLLAPSED THROUGHOUT THE STORE, CREATING HAZARDOUS CONDITIONS F
- Roof and weather protection · 39203621XSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ATOI, OBSERVED EXPS 1, 4, & 3 IN DISREPAIR. EXP1, WOODEN SUPPORT FOR GARAGE
- Windows, doors and openings · 35730930ZSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. NOTED: OBSERVED AT EXP 2(E. ELEV) OBSERVED BROKEN WINDOWS AT MULTIPLE LOC
- Boiler device inspection and filing · 39159344LSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING AND ALL PARTS THERE OF IN CODE COMPLAINT MANNER. NOTED; AT CELLAR LEVEL BOILER ROOM DOOR OF A MULTIPL
- Structural and interior building component · 39203454HSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED HOLE PENETRATIONS IN SERVER ROOM. LOCATED ON 3 FLOOR. PREVIOUS VIO
- Elevator safety and service status · 39202377ZSection 28-301.1 / OATH code 251 · FAILURE 2 CLASS RTS TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. REME
- Elevator safety and service status · 39203711JSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR IN BUILDING CODE COMPLIANT AS PER BC 3001.2 & 27-987 UPON AN INSPECTION THE ELEVATOR IS FOUND TO BE O
- Fire prevention or detection system · 39203844NSection 28-301.1 / OATH code 102 · ATOI OBSERVED LACK OF SPRINKLER COVERAGE ON ALL FLOORS IN THE HALLWAY OF THE ELEVATOR. CONTRARY TO BC 903.3.3 OBSTRUCTED LOCATIONS
- Windows, doors and openings · 39203466PSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION - BSMT APT B1 WAS OBSERVED W/O A 2ND EGRESS DU
- Fire prevention or detection system · 39203555RSection 28-301.1 / OATH code 251 · CLASS 2 ITEMS: FIRE EXTINGUISHER IN MACHINE ROOM IS EXPIRED/NOT PROPERLY MAINTAINED, IN VIOLATION OF NYC FIRE CODE 906 AND NFPA 10
- Authorized use versus observed occupancy · 39203683LSection 28-301.1 / OATH code 102 · ATOI, OBSERVED AT SEVERAL LOCATIONS WITHIN THE CELLAR/1ST-FLOOR FLOOR AND CEILING ASSEMBLY, SECTIONS OPENED WITH REQUIRED FIRESTOP
- Boiler device inspection and filing · 39143123LSection 28-301.1 / OATH code 254 · WEIL MCLAIN BOILER MODEL# EG75. MISSING OUTSIDE FRESH AIR IN BOILER ROOM. CORRECT VIOLATING CONDITION AND SUBMIT A CERTIFICATE OF
- Unprotected openings and fall exposure · 39203751YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN EXTERIOR OF BUILDING. AT TIME OF INSPECTION OBSERVED GUTTERS AT EXPOSURE 4 ROOF LINE IN A STATE OF DISREPAIR A
- Masonry or façade deterioration · 35730150HSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.-NOTE: AT TIME OF INSPECTION I OBSERVED AT EXP #1 WEST (1)CRACKED DETERIORATED M
- Masonry or façade deterioration · 39203882YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING EXTERIOR WALL IN A CODE-COMPLIANT. OBSERVED MULTIPLE MISSING, CRACKED AND DAMAGED EXTERIOR FACADE TIL
- Elevator safety and service status · 39203159PSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR IN BUILDING CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON AN INSPE
- Masonry or façade deterioration · 39203481NSection 28-301.1 / OATH code 102 · OBSERVED PLYWOOD FACADE SEVERELY DETERIORATED AT EXP #1, HOLES OBSERVED AT EXPOSURE# 3 IN THE FACADE AND EXP # 2 LOOSE SOLAR PANNE
- Gas equipment or fuel piping · 39203872KSection 28-301.1 / OATH code 102 · ATOI OBSERVED GAS METER BEING HOUSED IN THE FIRE PUMP ROOM WHICH IS CONTRARY TO BC 913.2.1 GAS PIPING, GAS CONSUMPTION DEVICES, GA
- Masonry or façade deterioration · 39144801XSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. NOTED AT GARAGE. OBSERVED GARAGE IS IN DETERIORATING CONDITION. OBSERVED
- Elevator device maintenance and safety devices · 39203645KSection 28-301.1 / OATH code 251 · CLASS 2 ITEMS: ELEVATOR CAR NOT PROVIDED WITH REQUIRED TWO-WAY EMERGENCY COMMUNICATION SYSTEM. PROVIDE A COMPLIANT TWO-WAY COMMUNI
- Plumbing fixture and drainage configuration · 39203500JSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED; BUILDING OBSERVED HAVING GUTTER LEADER AT LEFT SIDE (EXPOSURE-2) ALL
- Elevator safety and service status · 39203239PSection 28-301.1 / OATH code 251 · 1) THE PHONE IS NOT WORKING (RC)(8.11.2.1.1). 2) THE LIGHT IN THE OVERHEAD IS NOT WORKING. REMOVE DEBRIS (CLOTHES, ETC {6H}) FROM
- Elevator safety and service status · 39203792KSection 28-301.1 / OATH code 151 · CEASE USE ORDER: DOOR-ZONE RESTRICTOR IS BYPASSED, RENDERING THE REQUIRED DOOR-RESTRICTION FUNCTION INEFFECTIVE. CLASS 2 ITEMS: HO
- Safe building maintenance · 39203559YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MATTER. NOTED: AT EXP-1 AC UNITS INSTALLED THROUGHOUT W/O NYC REQUIRED BRACKETS., R
- Elevator safety and service status · 39203710HSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR IN BUILDING CODE COMPLIANT AS PER BC 3001.2 & 27-987. CLASS 1 VIOLATION: ELEVATOR DOOR IS CLOSING AT
- Elevator device maintenance and safety devices · 39203527JSection 28-301.1 / OATH code 251 · CLASS 2 ITEMS: EXCESSIVE MOVEMENT OBSERVED AT CAR GUIDE SHOES, INDICATING IMPROPER GUIDANCE ALONG RAILS. EQUIPMENT NOT MAINTAINED
- Electrical installation and permit · 39203455JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED COMBUSTIBLE STORAGE IN ELECTRICAL ROOM/SERVER ROOM. LOCATED ON 3RD
- Windows, doors and openings · 39203870RSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED AT EXPOSURE 1(FRONT) & 2(LEFT) AT 1ST & 2ND
- Roof and weather protection · 39203890YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: THE ROOF HAS BECOME POROUS ALLOWING RAINWATER TO ENTER DAMAGING THE
- Masonry or façade deterioration · 39203468ZSection 28-301.1 / OATH code 102 · OBSERVED AT EXP 1 FRONT OF THE BUILDING THE ROOF SINGLES AT SECOND LEVEL REMAINS IN A STATE OF DISREPAIR AND AT EXP 2 OBSERVED LAR