Examples under OATH infraction code 102
535 distinct enforcement-description examples carrying this infraction code. Check the actual summons before interpreting the code.
- Means of egress and exit protection · 39197575XSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION - EMERGENCY EGRESS WAS OBSERVED OBSTRUCTED: BA
- Safe building maintenance · 39204698ZSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER FOR VIOLATION #39160353L. OBSERVED AT EXPOSURE 1 ON GRAHAM AVENUE SHED POST
- Windows, doors and openings · 39203187MSection 28-301.1 / OATH code 102 · FRONT BUILDING IN DISREPAIR WITHOUT ROOF AND WINDOWS LEAVING BUILDING OPEN TO ELEMENTS AND WILDLIFE. CAUSING A SERVE STRUCTURAL AN
- Roof and weather protection · 39203188YSection 28-301.1 / OATH code 102 · FRONT BUILDING SIDING AND ROOF IN DISREPAIR, SIDING MISSING SECTIONS WHICH IS A SEVERE FALL HAZARD THAT CAN LEAD TO INJURY OR DEAT
- Masonry or façade deterioration · 39165269LSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION, OBSERVED LOOSE AND MISSING BRICK & MORTAR AT 3RD FLOOR LEVEL. DILAPIDATING FACADE IS POTENTIALLY CAUSING HA
- Windows, doors and openings · 39204010LSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF REINSPECTION FOR VIO#39185817L OBSERVED AT EXP#3 PARKING AREA CR
- Roof and weather protection · 39204017YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF REINSPECTION FOR VIO#339091087L,39151276M. OBSERVED IN COURT YAR
- Windows, doors and openings · 35718869RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER.OBSERVED HAZARDOUS CONDITIONS AT EXPOSURE 1 ON EAST 175 ST SUCH AS MASONRY
- Authorized use versus observed occupancy · 35721963KSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A SAFE CONDITION. AT TIME OF INSPECTION, OBSERVED PARTIAL COLLAPSE OF THE FLOOR ASSEMBLY AT THE IN
- Structural and interior building component · 35718762RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. I OBSERVED HAZARDOUS CONDITIONS ABOVE ENTRYWAY INTO STONE, DISLODGED CEILIN
- Masonry or façade deterioration · 35718693MSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. 5 SHORTY, BRICK M. D. BUILDING ON INTERIOR LOT. OBSERVED LARGE VERTICAL C
- Masonry or façade deterioration · 35721962ZSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING EXTERIOR IN A SAFE CODE-COMPLIANT CONDITION. AT TIME OF INSPECTION OBSERVED DETERIORATED EXTERIOR BRI
- Authorized use versus observed occupancy · 39196912NSection 28-301.1 / OATH code 102 · ATOI LOCATED IN BASEMENT PVC USED FOR DRAINAGE WHICH IS CONTRARY TO PC 1101.10 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANN
- Fire prevention or detection system · 39180293RSection 28-301.1 / OATH code 102 · OBSERVED AT CELLAR LEVEL SPRINKLER ROOM THE OS AND Y VALVE IS CLOSED SHOULD BE OPEN AND CHAINED LOCKED IN OPEN POSITION AND WATER
- Fire prevention or detection system · 35728398ZSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ATOI OBSERVED SPRINKLER SYSTEM THAT RUNS THROUGH HALLWAY COMPROMISED DUE TO
- Masonry or façade deterioration · 35728154MSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED AT EXPOSURE #4 THE SECTION OF STUCCO HAVE DETACHED AT LOWER SECTIO
- Safe building maintenance · 39204645PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLAINT MANNER. OBSERVED EXCESSIVE DEBRIS THROUGH OUT EXTERIOR OF PREMISES AT EXP 2,3 AND 4
- Authorized use versus observed occupancy · 39180356PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN IN A CODE-COMPLIANT MANNER. NOTE: - AT TIME OF INSPECTION, OBSERVED/ NOTED: AT CELLAR - 1ST FLOOR JOISTS/ROTTE
- Earlier order and correction filing · 39197897ZSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED MANY CRACKS IN STRUCTURE OF GARAGE ALSO FAILURE TO SUBMIT A CERTIFICATE OF CORRECTION OF VIOLATION
- Means of egress and exit protection · 39083962KSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED 1.) FIRE ESCAPE DROP LADDER OBSTRUCTED. 2.)
- Windows, doors and openings · 39172806NSection 28-301.1 / OATH code 102 · SUMMONS ISSUED FOR FAILURE TO MAINTAIN DUE TO WINDOW MOUNTED AIR CONDITIONER NOT SECURE PROPERLY AT THE 7TH FLOOR LEFT SIDE AT EXP
- Roof and weather protection · 39143242YSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED 2 WORKERS WORKING AT ROOF LEVEL WITHOUT REQUIRED HARNESS AND LIFELINE., REPAIR AND/REPLACE
- Structural and interior building component · 39135539PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. NOTE: AT TIME OF INSPECTION, OBSERVED/NOTED: AT FIRST FLOOR, REAR(NORTH)
- Structural and interior building component · 39197191RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER. OBSERVED AT EXP #2 WOODEN STAIRCASE IN STATE OF DISREPAIR. MISSING STEPS, H
- Zoning, site use or regulated sign · 39196606PSection 28-301.1 / OATH code 102 · ATOI, A SIGNIFICANT AMOUNT OF CONSTRUCTION DEBRIS WAS OBSERVED PILED UP IN FRONT OF THE COMMERCIAL SPACE INSIDE . THIS CONDITION R
- Masonry or façade deterioration · 39197566YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING FACADE. AT THE TIME OF INSPECTION, OBSERVED VERTICAL CRACKS AT EXPOSURE 1 SPANNING MULTIPLE STORIES,
- Safe building maintenance · 39161672NSection 28-301.1 / OATH code 102 · EXCESSIVE DEBRIS AT EXPOSURE 1.., REPAIR AND/REPLACE
- Masonry or façade deterioration · 39158882YSection 28-301.1 / OATH code 102 · OBSERVED IN APT#5H MINOR WATER DAMAGE TO CEILING, HOWEVER OBSERVED VERTICAL AND STEP CRACKS ON FACADE AT EXPOSURE#4 NEAR PARAPET L
- Masonry or façade deterioration · 35721788MSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AS NOTED: AT TIME OF INSPECTION OBSERVED PARAPET WITH CRACKS IN MASONRY AND
- Masonry or façade deterioration · 35689728NSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION IT WAS OBSERVED DAMAGED LINTELS, CRACKS AND DETERIORA
- Authorized use versus observed occupancy · 39190055KSection 28-301.1 / OATH code 102 · OBSERVE THAT CELLAR LEVEL EXPOSURE TO FOUR WALLS HAS BECOME POROUS WITH WATER DAMAGE AT VARIOUS LOCATIONS OF WALL., REPAIR AND/REP
- Masonry or façade deterioration · 39198936RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING CODE COMPLIANT. NOTED: THE PARTIAL RETAINING AT WALL AT LEFT SIDE BREEZEWAY IS IN SEVERE DISREPAIR WI
- Masonry or façade deterioration · 39164673ZSection 28-301.1 / OATH code 102 · SUMMONS ISSUED FOR FAILURE TO MAINTAIN DUE TO MULTIPLE CRACKS ON THE REAR FACADE OF STRUCTURE, REPAIR AND/REPLACE
- Plumbing fixture and drainage configuration · 39198405HSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED AT INCIDENT AT APARTMENT 6C RISER PIPE IN WALL BURST IN BATHROOM WALL FLOODING APARTMENT. THE EFFEC
- Authorized use versus observed occupancy · 39152862JSection 28-301.1 / OATH code 102 · PREVIOUS CORRECTIVE ACTION ISSUED 8/9/24 #3273-PREMISES MUST BE BUILT PER APPROVED C OF O #170915, WHICH DESIGNATES A LEGAL TWO-FA
- Means of egress and exit protection · 39164585ZSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION, OBSERVED MULTIPLE INFRACTIONS FOR FAILURE TO MAINTAIN OF PUBLIC/OCCUPANT SAFETY. NOTICED BLOCKED FIRE ESCAP
- Structural and interior building component · 35727890XSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. FAILURE TO PROVIDE NATURAL LIGHT AND VENTILATION FOR EVERY BEDROOM. NOTED:
- Electrical installation and permit · 39181432MSection 28-301.1 / OATH code 102 · AT FRONT FACADE ELECTRICAL WIRES EXPOSED AT MULTIPLE LOCATIONS CONDUIT PIPE FROM BASEMENT IS BROKEN/DETACHED. BASEMENT DOOR HAS BX
- Masonry or façade deterioration · 35718699NSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. 1-STORY INDUSTRIAL BUILDING ON INTERIOR LOT. OBSERVED DISLODGED BRICKS AB
- Zoning, site use or regulated sign · 39171131JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLAINT MANNER. ATOI, OBSERVED EXCESSIVE AMOUNT OF CONSTRUCTION DEBRIS, GARBAGE AT FRONT
- Zoning, site use or regulated sign · 39140844HSection 28-301.1 / OATH code 102 · REAR CMU IS IN DISREPAIR AND UPPER ROW WAS DISLODGED INTO 297 SHEPHARD AVENUE REAR YARD, DAMAGING SHED AND TRAMPOLIN, REPAIR AND/R
- Masonry or façade deterioration · 39197339YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. ATOI I OBSERVED AT FRONT YARD AT EXPOSURE#1 EXCEEDS AMOUNT OF DEBRIS, Q DEC
- Masonry or façade deterioration · 35731036ZSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTE: OBSERVED AT EXPOSURE 4(EAST) CRACKED STUCCO COATING IN MULTIPLE LOCAT
- Windows, doors and openings · 35730154PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. NOTE: AT TIME OF INSPECTION I OBSERVED AT EXP #1 WEST, #2 NORTH-CRACKED BRICK/S
- Earlier order and correction filing · 39161293NSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED AT EXPOSURE # 1 CRACKS IN BRICKS OF THE FACADE AND CORNICE DETERIORATING ,FAILURE TO COMPLY AND SUB
- Electrical installation and permit · 39197910YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED SIGN HAD FALLEN AT EXPOSURE 1 OF PROPERTY BLOCKING PEDESTRIAN WALK
- Boiler device inspection and filing · 35685893ZSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED AT 1ST FLOOR UNPROTECTED/EXPOSED ELECTRICAL WIRING EXIT PASSAGEWAY TO BACK OF THE BUILDING PARTIALL
- Structural and interior building component · 35729492JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. FAILURE TO PROVIDE REQUIRED NATURAL LIGHT AND VENTILATION FOR EVERY BEDROOM
- Authorized use versus observed occupancy · 39200044LSection 28-301.1 / OATH code 102 · ATOI OBSERVED AT CELLAR & BASEMENT PIPING PENETRATING FIRE-RATED WALLS WITHOUT REQUIRED FIRESTOPPING. OPENINGS REMAIN UNPROTECTED,
- Gas equipment or fuel piping · 39200303RSection 28-301.1 / OATH code 102 · ATOI OBSERVED THAT THE BUILDING ENCLOSURE AT THE GAS METER LOCATION WAS NOT MAINTAINED IN ACCORDANCE WITH THE APPROVED PLAN FILED
- Fire prevention or detection system · 35729495PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED AS PER BC 903.2 AND
- Masonry or façade deterioration · 39197083JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ATIO FOR VIO#39185955J. OBSERVED MULTIPLE STEP CRACKS AND ROTTED LENTILS AT
- Safe building maintenance · 39203052PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED UNSAFE CONDITION DUE TO THE ACCUMULATION OF COMBUSTIBLE MATERIALS (WO
- Means of egress and exit protection · 39203013MSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING. OBSERVED EXCESSIVE AMOUNTS OF COMBUSTIBLE DEBRIS AT REAR OF BUILDING; ALSO FOUND SECOND MEANS OF EGR
- Authorized use versus observed occupancy · 39177734XSection 28-301.1 / OATH code 102 · SUMMONS ISSUED FOR FAILURE TO MAINTAIN DUE TO SUPPORT BEAMS AT CELLAR LEVEL ROTTED, OUT OF PLUMB AND IN A STATE OF DISREPAIR., REP
- Means of egress and exit protection · 39168807NSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED FIRE ESCAPE DROP LADDER OBSTRUCTED WITH STAIRCASE. LOCATED EXPOSUR
- Masonry or façade deterioration · 39173693KSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: FACADE IN STATE OF DISREPAIR. AT EXP-4 TOP OF WALL MISSING BRICKS, S
- Safe building maintenance · 39181924ZSection 28-301.1 / OATH code 102 · AT THE TIME OF INSPECTION, AN EXCESSIVE AMOUNT OF CONSTRUCTION DEBRIS WAS PILED UP AT THE REAR OF THE PROPERTY (EXPOSURE THREE), P
- Safe building maintenance · 39196671LSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT THE TIME OF INSPECTION OBSERVED 1 STORY WOOD FRAME GARAGE LEANING
- Structural and interior building component · 39166238NSection 28-301.1 / OATH code 102 · ATOI INSPECTION OBSERVED THAT MULTIPLE FLOORS AND STAIRWAYS ARE UNEVEN AND SLOPED, CREATING HAZARDOUS CONDITIONS FOR THE TENANTS O
- Fire prevention or detection system · 35725700RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED AS PER BC 903.2 A
- Masonry or façade deterioration · 35717774JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. NOTE:-AT THE TIME OF INSPECTION OBSERVED: AT EXP #1 AND 2 EAST AND SOUTH
- Masonry or façade deterioration · 39164843MSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED CRACKED/SPALLING STUCCO AT MULTIPLE LOCATIONS AT ALL EXP'S (ALL SIDES OF BUILDING). ALSO MULTIPLE V
- Fire prevention or detection system · 35688423HSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF A AUTOMATIC SPRINKLER SYSTEM. WHERE REQUIRED PER BC 903.2 27-954 FO
- Fire prevention or detection system · 39180882PSection 28-301.1 / OATH code 102 · OBSERVED, PAINTED SPRINKLER CAPS ON THE SECOND FLOOR. LAUNDRY ROOM ON SECOND FLOOR EXHAUST VENT NOT INSTALLED PROPERLY. MISSING TR
- Safe building maintenance · 39180459HSection 28-301.1 / OATH code 102 · NOTED MARQUE AT FRONT EXPOSE IN DISREPAIR. SECTIONS OF CLADDING ARE MISSING OR LOSE. LOOSE ITEMS CREATE A FALLING DEBRIS HAZARD FO
- Zoning, site use or regulated sign · 39202603HSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ATOI, OBSERVED VACANT LOT WITH A LAKE. INSTALLED CHAIN-LINK FENCE AT LOT'S
- Plumbing fixture and drainage configuration · 39180881NSection 28-301.1 / OATH code 102 · OBSERVED REQUIRED 5 YEAR HYDROSTATIC PRESSURE TEST OF THE STANDPIPE SYSTEM WAS NOT AVAILABLE DURING TIME OF INSPECTION WHICH IS CO
- Masonry or façade deterioration · 39160719RSection 28-301.1 / OATH code 102 · ATOI OBSERVED AT REAR OF PROPERTY EXP 3, A 6' HIGH MASONRY WALL SEVERELY LEANING TOWARDS ADJOINING PROPERTY. WALL IS APPROX 120' L
- Windows, doors and openings · 39165233JSection 28-301.1 / OATH code 102 · OBSERVED: MULTIPLE WINDOW-MOUNTED AIR CONDITIONING UNITS INSTALLED ON SECOND & 1ST FLOOR LEADING INTO BARBER SHOP WINDOWS WITHOUT
- Authorized use versus observed occupancy · 35719519LSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. FAILURE TO PROVIDE THE REQUIRED NATURAL LIGHT AND VENTILATION PER EVERY B
- Safe building maintenance · 39202682PSection 28-301.1 / OATH code 102 · ATOI OBSERVED AT EXPOSURE 2 UNPROTECTED STEPS MISSING GUARD RAIL/ FENCE TO PREVENT FALL HAZARD., REPAIR AND/REPLACE; REPAIR AND/RE
- Roof and weather protection · 39162358JSection 28-301.1 / OATH code 102 · 2 STORY NFP BUILDING. OBSERVED TWO BICYCLES BLOCKING HALLWAY AND SCOOTER AND OTHER MATERIALS BLOCKING FIREMAN'S LADDER TO ROOF LEV
- Masonry or façade deterioration · 35685646LSection 28-301.1 / OATH code 102 · ATOI SECTION OF BRICKWALL ON PROPERTY LOT LINE PARTIALLY COLLAPSED AT CORNER OF EXPOSURE 3, 4 NEXT TO DRIVEWAY ENTRANCE TO PARKING
- Safe building maintenance · 39141421KSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER: AT TIME OF INSPECTION OF A EMPTY LOT, OBSERVED PADLOCKED AND STALLED CONS
- Structural and interior building component · 39182188YSection 28-301.1 / OATH code 102 · OBSERVED BILCO DOOR AT GROUND FLOOR ON STREET LEVEL. SECTION OF DOOR HAS ROTTED OUT AND RUST., REPAIR AND/REPLACE
- Masonry or façade deterioration · 39162190PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLAIN MANNER; NOTED EXP #4 CORNICE IS HEAVILY CORRODED WITH SECTIONS MISSING, 8'-0" LONG V
- Safe building maintenance · 39167385HSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MATTER. NOTED: AT EXP-1, A WOOD CORNICE IN STATE OF DISREPAIR WITH LOOSE AND MISSIN
- Construction fencing or site enclosure · 39181819RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING AND PARTS THEREOF IN A CODE-COMPLAINT MANNER. AT TIME OF INSPECTION, OBSERVED CORNER LOT CHAIN LINK F
- Masonry or façade deterioration · 39181962JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN. OBSERVED MULTIPLE SECTIONS OF THE FACADE AT EXPOSURE#1, LOOSE, MISSING AND IN DISREPAIR, REPAIR AND/REPLACE;