1,428 distinct descriptions associated with this law label in the October 2026 enforcement extract. These are source allegations with educational draft analyses, not verified outcomes.
- Fire prevention or detection system · 35729495PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED AS PER BC 903.2 AND
- Boiler device inspection and filing · 39200300LSection 28-301.1 / OATH code 239 · AT THE CELLAR AND BASEMENT, BOILER ROOM AND COORIDORS PIPING WAS OBSERVED PENETRATING FIRE-RATED CEILING AND WALLS. THE PENETRATIO
- Masonry or façade deterioration · 39197083JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ATIO FOR VIO#39185955J. OBSERVED MULTIPLE STEP CRACKS AND ROTTED LENTILS AT
- Boiler device inspection and filing · 39181738PSection 28-301.1 / OATH code 254 · FOUND SLANT FIN GAS FIRED BOILER MODEL # GGHT1500, WITH LEAKING RELIEF VALVE AND LABEL NOT LEGIBLE, COMBUSTION AIR FAN NOT OPERABL
- Unprotected openings and fall exposure · 39200042HSection 28-301.1 / OATH code 202 · ATOI AT EXPO #1, #3, AND INNER COURT ,OBSERVED SEVERAL WINDOW-MOUNTED A/C UNITS WITHOUT REQUIRED FALL PROTECTION OR ADEQUATE SECUR
- Safe building maintenance · 39203052PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED UNSAFE CONDITION DUE TO THE ACCUMULATION OF COMBUSTIBLE MATERIALS (WO
- Masonry or façade deterioration · 39200301NSection 28-301.1 / OATH code 202 · ATOI, AT THE REAR OF THE PROPERTY, OBSERVED AN APPROXIMATELY 10-FOOT-HIGH BY 60 FT WIDE RETAINING WALL. THE WALL IS SHOWING CRACKS
- Boiler device inspection and filing · 39155560HSection 28-301.1 / OATH code 254 · I FOUND A RHEEM XG75706ST76UO HOT WATER HEATER NOT OPERATIONAL, MAINTAIN BOILER; CORRECT ALL VIOLATING CONDITION/SUBMIT CERTIFICAT
- Elevator safety and service status · 39114072HSection 28-301.1 / OATH code 251 · ADJUST FLOOR STOPS. MISALIGNED CAB MIRROR. REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. ADJUST HOISTWAY DOOR ACCESS H
- Windows, doors and openings · 39199223LSection 28-301.1 / OATH code 202 · AT TIME OF INSPECTION OBSERVED A VIOLATING, FAILURE TO MAINTAIN, CONDITION FOR APPROXIMATELY 8 A/C UNITS PROTRUDING FROM WINDOWS W
- Windows, doors and openings · 39199228KSection 28-301.1 / OATH code 202 · ATOI - FAILURE TO MAINTAIN: MULTIPLE WINDOW A/C UNITS WERE OBSERVED AT THE EXTERIOR OF THE BUILDING ON EXPOSURES 1, 2, AND 4 WITHO
- Elevator device maintenance and safety devices · 39135517YSection 28-301.1 / OATH code 151 · CEASE USE ITEMS: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. DOOR LOCK MONITORING I
- Plumbing fixture and drainage configuration · 39181870MSection 28-301.1 / OATH code 302 · AT FIRST FLOOR COMMERCIAL SPACE "PJ TAX SERVICES" OBSERVED WATER DAMAGES (APPRX. 4 SF) TO THE CEILING IN THE BATHROOM AS A RESULT
- Boiler device inspection and filing · 39181737NSection 28-301.1 / OATH code 254 · FOUND LAARS GAS FIRED BOILER MODEL # PW0715 NOT OPERABLE , EXPOSED WIRING, HOT WATER STORAGE TANK MISSING AQUASTAT.
- Elevator device maintenance and safety devices · 39197884JSection 28-301.1 / OATH code 251 · 1) THE CAT-5 TAG IS MISSING FROM THE GOVERNOR. THE CAT-1 TAG IS EXPIRED. THE BRAKE TAG IS MISSING. THE ROPE TAG HAS NO DATE (8.11.
- Windows, doors and openings · 39181910HSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING CODE COMPLIANT. NOTED: THERE ARE CRACKS IN THE REAR WINDOW SILLS WITH LOOSE AND CRACKED CEMENT PARGIN
- Boiler device inspection and filing · 35668436ZSection 28-301.1 / OATH code 239 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3(2014 CODE); 27-345; BC 711.2.4(2022 CODE) FIR
- Means of egress and exit protection · 39203013MSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING. OBSERVED EXCESSIVE AMOUNTS OF COMBUSTIBLE DEBRIS AT REAR OF BUILDING; ALSO FOUND SECOND MEANS OF EGR
- Authorized use versus observed occupancy · 39168635XSection 28-301.1 / OATH code 189 · 3 STORY NFP BUILDING. OBSERVED AT CELLAR LEVEL ILLEGAL CLASS A APARTMENT WITH NO SECONDARY MEANS OF EGRESS AND BELCO DOOR LOCK FRO
- Windows, doors and openings · 39198477RSection 28-301.1 / OATH code 202 · I OBSERVED A FLEXIBLE LAUNDRY DRYER EXHAUST GOING THROUGH THE WINDOW IN THE APARTMENT 3C KITCHEN, WHICH IS NOT CODE COMPLIANT AS P
- Authorized use versus observed occupancy · 39177734XSection 28-301.1 / OATH code 102 · SUMMONS ISSUED FOR FAILURE TO MAINTAIN DUE TO SUPPORT BEAMS AT CELLAR LEVEL ROTTED, OUT OF PLUMB AND IN A STATE OF DISREPAIR., REP
- Means of egress and exit protection · 39168807NSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED FIRE ESCAPE DROP LADDER OBSTRUCTED WITH STAIRCASE. LOCATED EXPOSUR
- Masonry or façade deterioration · 39173693KSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: FACADE IN STATE OF DISREPAIR. AT EXP-4 TOP OF WALL MISSING BRICKS, S
- Elevator safety and service status · 39198495KSection 28-301.1 / OATH code 251 · CLASS 2 ITEMS: ELEVATOR MACHINE ROOM (EMR) ACCESS DOOR IS DAMAGED AND CANNOT BE PROPERLY CLOSED AND LOCKED. DOOR DOES NOT RESTRICT
- Windows, doors and openings · 39135576YSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN. APT.#1, BATHROOM CEILING HAS AN OPENING/MISSING SHEETROCK. 2ND FLOOR SKYLIGHT HAS WATER DAMAGE ON THE WALL.,
- Zoning, site use or regulated sign · 39178176PSection 28-301.1 / OATH code 302 · FAILURE TO MAINTAIN BUILDING AND PARTS THEREOF IN CODE COMPLIANT MANNER. NOTED : AT TIME OF INSPECTION ,OBSERVED AT FRONT OF PREMI
- Safe building maintenance · 39181924ZSection 28-301.1 / OATH code 102 · AT THE TIME OF INSPECTION, AN EXCESSIVE AMOUNT OF CONSTRUCTION DEBRIS WAS PILED UP AT THE REAR OF THE PROPERTY (EXPOSURE THREE), P
- Safe building maintenance · 39181046YSection 28-301.1 / OATH code 251 · : FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. REMEDY: RESTOR
- Safe building maintenance · 39196671LSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT THE TIME OF INSPECTION OBSERVED 1 STORY WOOD FRAME GARAGE LEANING
- Structural and interior building component · 39166238NSection 28-301.1 / OATH code 102 · ATOI INSPECTION OBSERVED THAT MULTIPLE FLOORS AND STAIRWAYS ARE UNEVEN AND SLOPED, CREATING HAZARDOUS CONDITIONS FOR THE TENANTS O
- Fire prevention or detection system · 35725700RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED AS PER BC 903.2 A
- Authorized use versus observed occupancy · 35720299RSection 28-301.1 / OATH code 189 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. LACK OF REQUIRED NUMBER OF MEANS OD EGRESS FOR EVERY FLOOR PER BC 1018.1(
- Masonry or façade deterioration · 35717774JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. NOTE:-AT THE TIME OF INSPECTION OBSERVED: AT EXP #1 AND 2 EAST AND SOUTH
- Elevator device maintenance and safety devices · 39204311PSection 28-301.1 / OATH code 151 · CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE (ASME A17.1-2013 / NYC APPENDIX K 2.26.1.40.1, 8.6.4.19). REMEDY: CORRECT AND EMA
- Authorized use versus observed occupancy · 35688422XSection 28-301.1 / OATH code 189 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OR REQUIRED NUMBER OF MEANS OF EGRESS FOR EVERY FLOOR PER BC 1018.1 27
- Safe building maintenance · 39195223NSection 28-301.1 / OATH code 302 · AT TIME OF INSPECTION FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER NOTED; SECTION OF CHAIN LINKED FENCE APPROXIMATELY 6FT
- Fire prevention or detection system · 39185157PSection 28-301.1 / OATH code 202 · OBSERVED AT TIME OF INSPECTION THAT THERE WAS NO SPRINKLER SYSTEM IN THE COMMERCIAL SPACE OCCUPIED BY BRONX VETERINARY CENTER. AS
- Zoning, site use or regulated sign · 39162901MSection 28-301.1 / OATH code 302 · FAILURE TO MAINTAIN IN CODE-COMPLIANT MANNER. CURB CUT WITHOUT DOB APPROVAL AS REQUIRED BY BC 3202.2.2.4 & DOT SPECIFICATIONS, HAZ
- Masonry or façade deterioration · 39164843MSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED CRACKED/SPALLING STUCCO AT MULTIPLE LOCATIONS AT ALL EXP'S (ALL SIDES OF BUILDING). ALSO MULTIPLE V
- Safe building maintenance · 39161537KSection 28-301.1 / OATH code 202 · FTM BUILDING AND ALL PARTS THEREOF IN CODE COMPLIANT MANNER : OBSERVED 2 COM. TRUCKS NY PLATE #76746-NE,76829-NE,1 TRUCK NY PLATE
- Construction fencing or site enclosure · 39156882PSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED AT REAR OF WAREHOUSE: 2 SECTIONS OF CHAIN LINK FENCE WITH BARBED WIRE
- Fire prevention or detection system · 35688423HSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LACK OF A AUTOMATIC SPRINKLER SYSTEM. WHERE REQUIRED PER BC 903.2 27-954 FO
- Fire prevention or detection system · 39180882PSection 28-301.1 / OATH code 102 · OBSERVED, PAINTED SPRINKLER CAPS ON THE SECOND FLOOR. LAUNDRY ROOM ON SECOND FLOOR EXHAUST VENT NOT INSTALLED PROPERLY. MISSING TR
- Elevator device maintenance and safety devices · 39203737HSection 28-301.1 / OATH code 251 · CLASS 2 ITEMS: CAR TOP IS NOT MAINTAINED IN A SAFE AND CODE-COMPLIANT CONDITION. REMOVE DEBRIS/OBSTRUCTIONS AND CORRECT DEFICIENCI
- Safe building maintenance · 39180459HSection 28-301.1 / OATH code 102 · NOTED MARQUE AT FRONT EXPOSE IN DISREPAIR. SECTIONS OF CLADDING ARE MISSING OR LOSE. LOOSE ITEMS CREATE A FALLING DEBRIS HAZARD FO
- Zoning, site use or regulated sign · 39202603HSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ATOI, OBSERVED VACANT LOT WITH A LAKE. INSTALLED CHAIN-LINK FENCE AT LOT'S
- Plumbing fixture and drainage configuration · 39180881NSection 28-301.1 / OATH code 102 · OBSERVED REQUIRED 5 YEAR HYDROSTATIC PRESSURE TEST OF THE STANDPIPE SYSTEM WAS NOT AVAILABLE DURING TIME OF INSPECTION WHICH IS CO
- Elevator safety and service status · 39202619MSection 28-301.1 / OATH code 251 · 1) AN ELEVATOR IN SECTION OF BUILDING OR BUILDING IS OUT-OF-SERVICE. UPON INSPECTION THE DEVICE IS FOUND TO BE OUT-OF-SERVICE. RES
- Masonry or façade deterioration · 39160719RSection 28-301.1 / OATH code 102 · ATOI OBSERVED AT REAR OF PROPERTY EXP 3, A 6' HIGH MASONRY WALL SEVERELY LEANING TOWARDS ADJOINING PROPERTY. WALL IS APPROX 120' L
- Windows, doors and openings · 39165233JSection 28-301.1 / OATH code 102 · OBSERVED: MULTIPLE WINDOW-MOUNTED AIR CONDITIONING UNITS INSTALLED ON SECOND & 1ST FLOOR LEADING INTO BARBER SHOP WINDOWS WITHOUT
- Safe building maintenance · 39189965LSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER NOTED: AT TIME OF INSPECTION OBSERVED TIRES IMPROPERLY STORED (NOT ON RACK
- Authorized use versus observed occupancy · 35719519LSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. FAILURE TO PROVIDE THE REQUIRED NATURAL LIGHT AND VENTILATION PER EVERY B
- Safe building maintenance · 39202682PSection 28-301.1 / OATH code 102 · ATOI OBSERVED AT EXPOSURE 2 UNPROTECTED STEPS MISSING GUARD RAIL/ FENCE TO PREVENT FALL HAZARD., REPAIR AND/REPLACE; REPAIR AND/RE
- Boiler device inspection and filing · 39135844LSection 28-301.1 / OATH code 154 · CEASE USE WEIL MCLAIN GAS FIRED STEAM BOILER, MODEL# UNKNOWN, DUE TO HAZARDOUS CONDITION,BURNERS CORRODED AND SMOKE HOOD FALLING O
- Zoning, site use or regulated sign · 39177725YSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. EXISTING CURB CUT HAS BEEN EXTENDED WITHOUT DOB APPROVAL AS REQUIRED BY B
- Roof and weather protection · 39162358JSection 28-301.1 / OATH code 102 · 2 STORY NFP BUILDING. OBSERVED TWO BICYCLES BLOCKING HALLWAY AND SCOOTER AND OTHER MATERIALS BLOCKING FIREMAN'S LADDER TO ROOF LEV
- Masonry or façade deterioration · 35685646LSection 28-301.1 / OATH code 102 · ATOI SECTION OF BRICKWALL ON PROPERTY LOT LINE PARTIALLY COLLAPSED AT CORNER OF EXPOSURE 3, 4 NEXT TO DRIVEWAY ENTRANCE TO PARKING
- Fire prevention or detection system · 39142756RSection 28-301.1 / OATH code 202 · OBSERVED ON THE ROOF WATER TANK LEAKING, SPRINKLER SYSTEM COMPROMISED ,LACK WATER PRESSURE IN THE SPRINKLER SYSTEM, TAMPER SWITCH
- Zoning, site use or regulated sign · 39155139YSection 28-301.1 / OATH code 302 · VEHICULAR ACCESS CURB CUTS THAT CAN NO LONGER SERVE AS A VEHICULAR ACCESS ACROSS A CURB OR SIDEWALK SHALL BE REMOVED AND RESTORED
- Safe building maintenance · 39141421KSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER: AT TIME OF INSPECTION OF A EMPTY LOT, OBSERVED PADLOCKED AND STALLED CONS
- Safe building maintenance · 39166173LSection 28-301.1 / OATH code 151 · UPON REINSPECTION, THE DEVICE IS FOUND TO BE OUT OF ORDER, BY THE COMMISSIONER ORDER, REMEDY REPAIR CEASE USE ITEMS, THEN CONTACT
- Structural and interior building component · 39182188YSection 28-301.1 / OATH code 102 · OBSERVED BILCO DOOR AT GROUND FLOOR ON STREET LEVEL. SECTION OF DOOR HAS ROTTED OUT AND RUST., REPAIR AND/REPLACE
- Masonry or façade deterioration · 39162190PSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLAIN MANNER; NOTED EXP #4 CORNICE IS HEAVILY CORRODED WITH SECTIONS MISSING, 8'-0" LONG V
- Safe building maintenance · 39167385HSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MATTER. NOTED: AT EXP-1, A WOOD CORNICE IN STATE OF DISREPAIR WITH LOOSE AND MISSIN
- Elevator safety and service status · 39182172JSection 28-301.1 / OATH code 151 · RTS CLASS 1: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE. REM
- Authorized use versus observed occupancy · 39171808MSection 28-301.1 / OATH code 126 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANN: USE OF PROHIBITED DOOR AND / OR HARDWARE PER BC 10008.1.8; 27-371(J). 5 DOORS
- Construction fencing or site enclosure · 39181819RSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING AND PARTS THEREOF IN A CODE-COMPLAINT MANNER. AT TIME OF INSPECTION, OBSERVED CORNER LOT CHAIN LINK F
- Masonry or façade deterioration · 39181962JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN. OBSERVED MULTIPLE SECTIONS OF THE FACADE AT EXPOSURE#1, LOOSE, MISSING AND IN DISREPAIR, REPAIR AND/REPLACE;
- Safe building maintenance · 39177569LSection 28-301.1 / OATH code 251 · VF... HOIST ROPE RUSTED REPLACE..62-K-11....
- Masonry or façade deterioration · 39190948HSection 28-301.1 / OATH code 202 · AT TIME OF INSPECTION OBSERVED EXPOSURE 1,2,3,4 FLOORS 1-2, VERTICAL, HORIZONTAL & STEP CRACKS IN MULTIPLE AREAS THROUGHOUT CREATI
- Plumbing fixture and drainage configuration · 39182843LSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING, OBSERVED IMPROPER DRAINAGE WITH (2) ROOF LEADER DOWNSPOUT AT FRONT, LEFT & RIGHT SIDES AT THIS LOCAT
- Permit posting at the inspection location · 39181979XSection 28-301.1 / OATH code 251 · CLASS 2 ITEMS: DAMAGED ECCENTRIC OBSERVED ON CAR DOOR REAR HANGER ROLLER, RESULTING IN IMPROPER DOOR ALIGNMENT AND POTENTIAL UNSAF
- Structural and interior building component · 39173725XSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED A DAMAGED FLOOR WITH MISSING FLOOR TILES I
- Means of egress and exit protection · 39179463MSection 28-301.1 / OATH code 202 · STRUCTURE RENDERED NON-COMPLIANT DUE TO FIRE AT 1234A E GUNHILL ROAD. NO STRUTURAL DEFECTS OBSERVED EGRESS INTACT., REPAIR AND/OR
- Authorized use versus observed occupancy · 39161277NSection 28-301.1 / OATH code 102 · ATOI OBSERVED OPEN PIT APPROX 7' DEEP INSIDE CELLAR OF 382 AUDUBON AVE. NO SHEETING , SHORING OR HANDRAILS;FIRESTOPPING MISSING ;
- Gas equipment or fuel piping · 39174899KSection 28-301.1 / OATH code 102 · ATOI OBSERVED IN APARTMENT 8 WATER, SANITARY AND GAS PIPES ALL UNCAP, WITH THE GAS METER NOT SHUT OFF BY UTILITY COMPANY AND CORRO
- Authorized use versus observed occupancy · 39174810PSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. ATOI OF APARTMENT 7 ON THE 4TH FLOOR, I OBSERVED DISCOLORATION AND WET SP
- Safe building maintenance · 39155345PSection 28-301.1 / OATH code 151 · CEASE USE ITEM: INOPERATIVE DOOR LOCK MONITORING AS REQUIRED BY CODE AT TIME OF INSTALLATION. CLASS 2 ITEMS: REPALCE WORN GIBS WHE
- Means of egress and exit protection · 39179572LSection 28-301.1 / OATH code 238 · INOPERABLE EMERGENCY EXIT LIGHTING OBSERVED AT DRINKING ESTABLISHMENT ON FIRST FLOOR AT BOTH EXIT DOORS. AS PER BC 1006.1;27-542.,
- Windows, doors and openings · 39167326HSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN PROPERTY IN CODE COMPLAINT MANNER; NOTED BUILDING IS VACANT AND UNGUARDED, AT EXPOSURE 3 CELLAR LEVEL THERE IS