Cases associated with NYC DOB 28-301.1
1,428 distinct descriptions associated with this law label in the October 2026 enforcement extract. These are source allegations with educational draft analyses, not verified outcomes.
- Means of egress and exit protection · 39137280YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: OBSERVED ACCORDING TO FILING #S007757787-P1 WHICH DEMONSTRATES THE 6FT REQU
- Plumbing fixture and drainage configuration · 39202147NSection 28-301.1 / OATH code 202 · ATOI OBSERVED IN BASEMENT PVC PIPE USED ON HOT WATER HEATER VENTING. PER PC 701.9 PLASTIC PIPE. PLASTIC PIPING AND FITTINGS SHALL
- Elevator safety and service status · 39201858PSection 28-301.1 / OATH code 151 · 97-X-17 THE ELEVATOR IN BUILDING OUT OF SERVICE UPON INSPECTION THE DEVICE IS FOUND TO BE OUT OF SERVICE CREATING A HAZARDOUS COND
- Safe building maintenance · 39201673ZSection 28-301.1 / OATH code 302 · FAILURE TO MAINTAIN BUILDING AND ALL PARTS THEREOF IN A CODE COMPLIANT MANNER . NOTED : AT TIME OF INSPECTION,OBSERVED AT EXPOSURE
- Wall / exterior structural condition · 39187975XSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING AND PARTS THERE OF IN A CODE COMPLIANT MANNER. NOTED; AT REAR OF PREMISES RETAINING WALL IN STATE OF
- Zoning, site use or regulated sign · 39201679JSection 28-301.1 / OATH code 251 · 5.1.21.1 EMERGENCY SIGNAL CAR PHONE INOPERATIVE, 58-H-10 MAIN MACHINE BEARING NEED TO RELPACE MAKING NOISE, PROVIDE SIGNAGE ON ALL
- Fire prevention or detection system · 39202203ZSection 28-301.1 / OATH code 102 · AT THE TIME OF INSPECTION OBSERVED THROUGHOUT THE BUILDING IN STORAGE ROOMS BOXES STACKED TO THE CEILING BLOCKING OPERATION OF SID
- Structural and interior building component · 39160351HSection 28-301.1 / OATH code 302 · NOTED: DETERIORATED STAIR TREAD/RISER AT FIRST FLOOR STAIR A., REPAIR AND OR REPLACE
- Tenant protection plan / occupied-site safeguards · 39201855JSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN AT TIME OF INSPECTION OBSERVED EXCESSIVE AMOUNT DUST IN THE HALLWAY AND STAIRS,HANDRAILS CREATING A HEALTH HAZ
- Safe building maintenance · 39201665ZSection 28-301.1 / OATH code 251 · REPAIR RAIL GUIDE SHOES. (8.6.4.3.2)
- Means of egress and exit protection · 39202008NSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING FIRE ESCAPE. AT TIME OF INSPECTION, OBSERVED AT EXPOSURE 1, FIRE ESCAPE LADDER BRACKET SECURING LADDE
- Masonry or façade deterioration · 39201630ZSection 28-301.1 / OATH code 102 · AS PER PREVIOUS REQUEST FOR CORRECTIVE ACTION ISSUED ON 04/10/2026 BY BADGE 2387 FOR AT ROOF TOP, ON THE LEFT SIDE OF BUILDING ,MA
- Safe building maintenance · 39201520HSection 28-301.1 / OATH code 302 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ATOI, OBSERVED FENCE GATE DOOR AJAR. PROPERTY IS OPEN TO THE PUBLIC. NOTE,
- Elevator safety and service status · 39202094ZSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR EQUIPMENT AS PER BC3001.2 & 28-987. RTS CLASS 1: UPON AN INSPECTION THE ELEVATOR IS FOUND TO BE OUT O
- Masonry or façade deterioration · 39201844YSection 28-301.1 / OATH code 102 · ATOI OBSERVED MULTIPLE CRACKS, SPALLING AND DETERIORATED CONCRETE/MASONRY AT THE FRONT STOOP, CONCRETE DISMISSING AND RAINWATER PE
- Safe building maintenance · 39202028KSection 28-301.1 / OATH code 151 · CEASE USE ITEMS: 1) NON WORKING DLM (A17.3 3.10.12.). BY PASSED PLANK SWITCH (2.18). 3) EXCESSIVE GAP BETWEEN RIGHT BRAKE PAD AND
- Zoning, site use or regulated sign · 39201699RSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING AND ALL PARTS THEREOF IN CODE COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION, OBSERVED AT EXPOSURE 1,
- Roof and weather protection · 39192827KSection 28-301.1 / OATH code 102 · AT THE REAR OF THE PROPERTY THE RESIDENTIAL HOUSE OBSERVED AT EXP 1 SECOND FLOOR A SLIDING DOOR LEADING OUT TO A FLAT ROOF WITH NO
- Authorized use versus observed occupancy · 39201712MSection 28-301.1 / OATH code 139 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. A
- Unprotected openings and fall exposure · 39202068PSection 28-301.1 / OATH code 102 · VIOLATION ISSUED FOR FAILURE TO MAINTAIN SAFETY MEASURES NO HANDRAIL SYSTEM AND GUARDRAIL SYSTEM . ATOI OBSERVED ON THE RESIDENT N
- Roof and weather protection · 39201820JSection 28-301.1 / OATH code 202 · RCA ISSUED 05/23/25 SAME RESPONDENT FAILURE TO MAINTAIN BLDG SAFE & CODE-COMPLIANT 28-301.1, RESPONDENT HAS NOT MADE ANY APPOINTME
- Structural and interior building component · 39201629LSection 28-301.1 / OATH code 202 · AT REAR OF 1ST FLOOR, BY SIDE DOOR, WATER SEEPAGE HAS CAUSED FINISHED CEILING TO PEEL FINISH., REPAIR AND/OR REPLACE
- Boiler device inspection and filing · 39201718NSection 28-301.1 / OATH code 254 · FOUND THREE WILLIAMSON MODEL-GWA075 BOILERS. MISSING PRIMARY LOW AND MANUAL LOW WATER CUTOFF'S, MISSING MANUAL RESET AQUA-STAT, MI
- Boiler device inspection and filing · 39201736RSection 28-301.1 / OATH code 254 · NATIONAL GRID SHUT OFF GAS DUE TO INOPERABLE HOT WATER HEATER, MAINTAIN BOILER; CORRECT VIOLATING CONDITION SUBMIT CERTIFICATE OF
- Elevator device maintenance and safety devices · 39201944LSection 28-301.1 / OATH code 251 · CLASS 2 ITEMS: IN-CAR COMMUNICATION INOPERATIVE. ASME A17.1 2.27.1. FIREFIGHTERS' SERVICE PHASE 2 INOPERATIVE. NEED TO REPLACE KEY
- Windows, doors and openings · 39201897HSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. ATOI, OBSERVED 1ST - 2ND FLOOR WINDOWS REMOVED, EXPOSING DAMAGED SHEETROC
- Elevator device maintenance and safety devices · 39201904RSection 28-301.1 / OATH code 251 · VF... COMMUNICATION DEFECTIVE REPAIR... 8.6.4.15... CONTROLLER FUSE BYPASSED REMOVE.. 8.6.4.8..... MAINTENANCE LOG UPDATE MISSING
- Zoning, site use or regulated sign · 39201714XSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING AND PARTS THEREOF IN A CODE-COMPLIANT MANNER. ATOI, OBSERVED AN EXCESSIVE AMOUNT OF GARBAGE, PLASTICS
- Means of egress and exit protection · 39201839JSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED AT INTERIOR FLOORS 1-BULKHEAD, LOBBY, STAIRW
- Windows, doors and openings · 39201580JSection 28-301.1 / OATH code 202 · AT TIME OF INSPECTION, OBSERVED AC UNITS INSTALLED AT WINDOWS OF EXPO 1 BLOCKING EGRESS TO ACCESS FIRE ESCAPE. EGRESS HAS BEEN COM
- Safe building maintenance · 39202067NSection 28-301.1 / OATH code 102 · NOTED: ECB VIOLATION ISSUED FOR FTM DUE TO EXCESSIVE DEBRIS. ATOI OBSERVED AN EXCESSIVE AMOUNT OF CONSTRUCTION DEBRIS PILED UP AT
- Elevator safety and service status · 39202048HSection 28-301.1 / OATH code 151 · FAILURE TO MAINTAIN ELEVATOR ASPER BC3001.2 & 27-987. UPON AN INSPECTION THE ELEVATOR IS FOUND OUT OF SERVICE CREATING A HAZARDOUS
- Plumbing fixture and drainage configuration · 39201941XSection 28-301.1 / OATH code 302 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT TIME OF INSPECTION. OBSERVED RAIN WATER LADDER DOWNSPOUT CONNECTE
- Roof and weather protection · 39201814NSection 28-301.1 / OATH code 202 · RCA ISSUED 04/04/25 SAME RESPONDENT FAILURE TO MAINTAIN BLDG IN SAFE & CODE COMPLIANT 28-301.1, RESPONDENT HAS NOT MADE ANY APPOIN
- Zoning, site use or regulated sign · 39201719PSection 28-301.1 / OATH code 202 · SIDEWALK CURB AT FRONT OF PROPERTY (EXP. 1) CUT, SO THAT PORTION OF SIDEWALK IS LOWERED ENABLING A VEHICLE TO DIVE UNTO ON ILLEGAL
- Zoning, site use or regulated sign · 39201874PSection 28-301.1 / OATH code 302 · FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. SIDEWALK CURB CUT APPROX. 8 FT AT FRONT OF PROPERTY (EXP. 1) PORTION OF S
- Safe building maintenance · 39193143YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION FOR VIO#39175695N OBSERVED AT EXP#1 CURD HAS BEEN LOW
- Masonry or façade deterioration · 39201976XSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION I OBSERVED ON FIRST FLOOR APART.1R AT REAR . I OBSERV
- Masonry or façade deterioration · 39201657ZSection 28-301.1 / OATH code 202 · AT EXP 1 AND 2 ENTRY STAIRS MISSING BRICKS AND LOOSE BRICKS AND HANDRAIL. CONDITION PRESENTS POTENTIAL FOR TRIPS AND FALLS WITH SE
- Zoning, site use or regulated sign · 39201596YSection 28-301.1 / OATH code 302 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLAINT MANNER. NOTED: AT TIME INSPECTION, OBSERVED ILLEGAL CURB CUT CREATED PAINTED IN YEL
- Plumbing fixture and drainage configuration · 39202205MSection 28-301.1 / OATH code 102 · ATOIOBSERVED PLASTIC PVC PIPING BEING USED FOR DRAINAGE UNDER 2 COMPARTMENT SINK WITH NO TRAP INSTALLED HAVING PVC FLEXIBLE PIP DR
- Plumbing fixture and drainage configuration · 39201751PSection 28-301.1 / OATH code 302 · FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANER NOTED; AT TIME OF INSPECTION, OBSERVED AT EXPOSURE 1 ROOF RAIN WATER LADDER
- Means of egress and exit protection · 39201778PSection 28-301.1 / OATH code 189 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: LACK OF REQUIRED NUMBER OF MEANS OF EGRESS FOR EVERY FLOOR PER BC 1018.1 (2
- Roof and weather protection · 39200772JSection 28-301.1 / OATH code 302 · FAILURE TO MAINTAIN BUILDING AND ALL PARTS THEREOF IN A CODE COMPLIANT MANNER . NOTED : AT TIME OF INSPECTION ,OBSERVED AT EXPOSUR
- Authorized use versus observed occupancy · 35728380KSection 28-301.1 / OATH code 126 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. USE OF PROHIBITED DOOR AND 1 HARDWARE BC 1008.1.8(2014), BC 1010.1.8(2022),
- Means of egress and exit protection · 39201916YSection 28-301.1 / OATH code 189 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER: LACK OF REQUIRED NUMBER OF MEANS OF EGRESS FOR EVERY FLOOR PER BC 1018.1 (2
- Masonry or façade deterioration · 39201654NSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. AT TIME OF INSPECTION OBSERVED AT EXPOSURE 1(FRONT) PATIO BOTTOM & STOOP RI
- Windows, doors and openings · 39201710ZSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING AND ALL PARTS THEREOF IN A CODE-COMPLIANT MANNER. ATOI, I OBSERVED THE BUILDING IN A STATE OF DISREPA
- Masonry or façade deterioration · 39161731YSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED STEP CRACKS ALONG WITH MISSING/SPALLING MORTAR JOINTS AT PARAPET LEVEL OF EXP.1(FRONT OF BUILDING).
- Masonry or façade deterioration · 39201680RSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. OBSERVED BULGING BRICK AND STEP CRACKS ABOVE ENTRY DOOR AT EXPOSURE 1 OF PR
- Windows, doors and openings · 39202211ZSection 28-301.1 / OATH code 102 · ATOI OBSERVED SIGNIFICANT AMOUNT OF BRICK HAS BEEN REMOVED AT EXPOSURE 2/4/1 LEAVING BAY WINDOW NOT PROPERLY SUPPORTED. ALSO OBSER
- Scaffold platform and fall protection · 39202126YSection 28-301.1 / OATH code 102 · ATOI OBSERVED AN UNSAFE AND POORLY MAINTAINED SUPPORTED SCAFFOLD WITH INADEQUATE TIE-INS, NON-COMPLIANT PLANKING, EXPOSED GUARDRAI
- Masonry or façade deterioration · 39202161JSection 28-301.1 / OATH code 102 · NOTED AT THE TIME OF INSPECTION, MULTIPLE STEP CRACKS WERE OBSERVED ALONG EXPOSURE #1 (FRONT OF THE PROPERTY), EXTENDING ACROSS MU
- Masonry or façade deterioration · 39161732XSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED CRACKED/SPALLING STUCCO AT MULTIPLE LOCATION OF EXP.3(REAR OF BUILDING). PARAPET WALL HAS LOOSE/MIS
- Masonry or façade deterioration · 39202054YSection 28-301.1 / OATH code 102 · AT TIME OF INSPECTION OBSERVED MULTIPLE CRACKS ON THE STUCCO AND MASONRY FACADE, MISSING BRICKS STEP CRACKS AT EXPOSURE #3 AND #4.
- Safe building maintenance · 39201655PSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN PROPERTY IN SAFE & CODE COMPLIANT MANNER 28-301., OBSERVED PORTION OF FENCE FALLING DOWN AT EXP 02 W/ REBAR PR
- Masonry or façade deterioration · 39201775JSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ATOI OBSERVED AT EXP#1&4 CRACKS IN STUCCO,AND A LARGE VERTICAL CRACK AT THE
- Wall / exterior structural condition · 39201802XSection 28-301.1 / OATH code 102 · NOTED AT THE TIME OF INSPECTION, THE SOFFIT UNDERNEATH THE THIRD-FLOOR BALCONY ALONG EXPOSURE#1 FRONT OF PROPERTY IS IN A STATE OF
- Fire prevention or detection system · 39202308PSection 28-301.1 / OATH code 102 · ATOI OBSERVED OBSTRUCTED SPRINKLER HEAD, DAMAGED, AND MISSING SPRINKLER CAPS THROUGH OUT THE BUILDING CONTRARY TO . BC 903.3.3 - O
- Elevator safety and service status · 39201728RSection 28-301.1 / OATH code 251 · 1) PROVIDE ACCESS TO MR TO CONDUCT A PROPER ELEVATOR INSPECTION. 2) ADJUST CAR DOOR SCRAPPING FACIA ON 5TH FLOOR. 3) PROVIDE CORRE
- Structural and interior building component · 39202274XSection 28-301.1 / OATH code 102 · NOTED AT THE TIME OF INSPECTION, THE WOODEN BALUSTER ALONG THE STAIRWAY FROM THE 3RD FLOOR LEADING TO THE 4TH FLOOR WAS OBSERVED T
- Roof and weather protection · 39201889HSection 28-301.1 / OATH code 251 · PROIVDE DESIGNATED LOBBY BRAILLE TAGS (ADA). PROVIDE CAB MIRROR. (BC 3001.6). REPLACE WORN GIBS WHERE NEEDED (2.11.11.5.7.). SEAL
- Zoning, site use or regulated sign · 39202099HSection 28-301.1 / OATH code 302 · AT THE TIME OF INSPECTION, OBSERVED VEGETATION OVERGROWTH OVERTAKING AND OBSTRUCTING THE SIDEWALK AND DESIGNATED PEDESTRIAN PATHWA
- Zoning, site use or regulated sign · 39202257YSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED BUILDING HAS BEEN OBSERVED AT THE SIDE AND REAR YARD OF THE BUILDING
- Elevator device maintenance and safety devices · 39202288RSection 28-301.1 / OATH code 151 · CLASS 1 C/U: 1. DOOR ZONE RESTRICTOR - DOOR ZONE RESTRICTOR INOPERATIVE, FAILING REQUIRED PREVENTION OF DOOR OPENING OUTSIDE THE D
- Electrical installation and permit · 39201812JSection 28-301.1 / OATH code 251 · PROIVDE DESIGNATED LOBBY BRAILLE TAGS (ADA). REPLACE OR SECURE GIBS WHERE NEEDED (2.11.11.5.7.). MISALINGED CAB MIRROR (BC 3001.2)
- Zoning, site use or regulated sign · 39201905ZSection 28-301.1 / OATH code 251 · 5.1.21.1 EMERGENCY SIGNAL CAR PHONE INOPERATIVE, MOROR ROOM DOOR LOCK MISSING PROVIDE, 5.3.1.2.2PIT MAINTANANCE PIT DIRTY CLEAN,
- Fire prevention or detection system · 39201693XSection 28-301.1 / OATH code 251 · MISSING CAB MIRROR (BC 3001.6). REPLACE WORN GIBS WHERE NEEDED (2.11.11.5.7.). INOPERATIVE CAR PHONE (2.27.1.1.3.). WATER IN PIT (
- Elevator device maintenance and safety devices · 39202177YSection 28-301.1 / OATH code 151 · VF... CEASE USED... DOOR RESTRICTOR NOT WORKING ..DOOR ZONE RESTRICTOR HAS BEEN TEMPERED WITH DISABLED INOPREATIVE . THIS ISASAFET
- Authorized use versus observed occupancy · 39201994JSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING AND ALL PARTS THEREOF IN A CODE-COMPLIANT MANNER. AT THE TIME OF INSPECTION OF APARTMENT 1R, I OBSERV
- Plumbing fixture and drainage configuration · 39160430XSection 28-301.1 / OATH code 102 · OBSERVED AT EXPOSURE#3 REAR YARD SLAB SINKING APPROXIMATELY 12" WITH STEEL BEAMS AND RETAINING WALL COMPROMISED. VACATE REAR YARD
- Elevator safety and service status · 39201824RSection 28-301.1 / OATH code 251 · 1) CLEANING OF ELEVATOR PIT. 2) ADJUST CAR DOOR SCRAPPING. 3) INOPERATIVE CAR PHONE. 4) PROVIDE ACCESS TO MR FOR PROPER ELEVATOR I
- Structural and interior building component · 39202174ZSection 28-301.1 / OATH code 251 · 1) THE PHONE IS NOT WORKING (RC)(8.11.2.1.1). 2) THERE ARE SEVERAL DOOR ROLLER (ON SEVERAL FLOORS) THAT ARE WORN (8.11.2.1.3). 3)
- Fire prevention or detection system · 35725736ZSection 28-301.1 / OATH code 102 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. LACK OF A SYSTEM OF AUTOMATIC SPRINKLERS WHERE REQUIRED AS PER BC 903.2 A
- Zoning, site use or regulated sign · 39202075NSection 28-301.1 / OATH code 251 · 1) THE CAT-1 TAG IS EXPIRED (8.11.1.6) 2) THE PEDESTAL BEARING IS SHOWING SIGNS OF WEAR (8.11.2.1.2).
- Safe building maintenance · 39137281XSection 28-301.1 / OATH code 202 · FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER: AT THE TIME OF INSPECTION, OBSERVED AT REAR OF PROPERTY, ADA RAMP FOR RES
- Roof and weather protection · 39201662NSection 28-301.1 / OATH code 251 · MISALINGED CAB MIRROR (BC 3001.6). REPLACE OR SECURE GIBS WHERE NEEDED (2.11.11.5.7.). MISSING IN CASE OF FIRE SIGN IN LOBBY (BC 3
- Authorized use versus observed occupancy · 35725735RSection 28-301.1 / OATH code 189 · FAILURE TO MAINTAIN BUILDING IN A CODE-COMPLIANT MANNER. LACK OF THE REQUIRED NUMBER OF MEANS OF EGRESS FOR EVERY FLOOR AS PER BC
- Windows, doors and openings · 39177038MSection 28-301.1 / OATH code 102 · OBSERVED AT SEVERAL LOCATIONS AT EXTERIOR OF BUILDING WITH DEFECTS THAT INCLUDE. STEP CRACKS AROUND BRICKS AND SECTIONS OF DECORAT
- Safe building maintenance · 39202176MSection 28-301.1 / OATH code 202 · OBSERVED IN APT 2A PROHIBITED PVC PIPING AND FITTINGS CONNECTED TO KITCHEN DRAIN AS PER NYC PC 701.9, ALSO OBSERVED UNSHIELDED RUB
← Previous Page 14 of 18 Next →